Plan Review Notes
Plan Review Notes For Permit 22120561
Permit Number 22120561
Review Stop M
Sequence Number 1
Notes
Date Text
2023-01-06 08:08:491ST REVIEW FMC
 PERMIT: 22120561
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW
 BUILDING. FEC C401.2
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS NEW BUILDING. FEC C403.2.1
  
 3) SHEET M-100: PROVIDE THE OUTDOOR AIR DUCT SIZE FOR
 AHU-1. FBC 107.3.5
  
 4) SHEET M-102: SHOW GUARD PROTECTION FOR ALL EQUIPMENT
 ON THE ROOF THAT IS WITHIN 10 FEET FROM THE ROOF EDGE.
 FMC 304.11
  
 5) SHEET M-600: THE 168 SQ. FT. LOBBY WOULD ACCOMMODATE
 26 OCCUPANTS AND REQUIRE 140 CFM???S OF OUTDOOR AIR,
 PLEASE MODIFY THE SCHEDULES TO MEET THIS REQUIREMENT.
 FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  