Plan Review Notes
Plan Review Notes For Permit 22120561
Permit Number 22120561
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-10 07:58:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22120561
 ADD: 915 N. RAILROAD AVE.
 CONT: HEDRICK BROTHERS CONSTRRUCTION
 TEL: 561-308-2954
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 04TH/2023
 ACTION: DENIED
  
 1) SHEET T100 TITLE SHEET:
 1A) PROJECT DESCRIPTION THE EXISTING BUILDING IS
 DEMOLISHED WITH EXCEPTION OF THE NORTH AND OR SOUTH
 WALLS TO REMAIN. NEW BUILDING IS PROPOSED IN ITS PLACE.
 2020 EXISTING BUILDING CODE SECTION 907.4.1.
 (ALTERATION LEVEL LLL ALTERATION) EVALUATION AND
 ANALYSIS. AN ENGINEERING EVALUATION AND ANALYSIS THAT
 ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED
 STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. HOW
 WILL THE 2 STORY SIDE WALLS AND FOOTER BE KEPT FROM
 OVERTURNING DURING CONSTRUCTION. EVERY STRUCTURE SHALL
 BE DESIGNED TO RESIST THE OVERTURNING POSITIVE &
 NEGATIVE EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED
 IN THIS CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
  
 1B) 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1C) BUILDING PROVISO: DEFERRED SUBMITTALS:
 COMPONENTS & CLADDING.
 (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: CURTAINWALL, STOREFRONTS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) PRE-ENGINEERED ROOFTOP A/C STANDS
 STAIR & ELEVATOR SHOP DRAWINGS
 ROOF ACCESS LADDER SHOP DRAWINGS
 FRONT CANOPY SHOP DRAWINGS
 STEEL SHOP DRAWINGS
  
 1D) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 1E) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
  
 2) SHEET S001 GENERAL NOTES: GEOTECHNICAL INVESTIGATIVE
 REPORT. PLEASE PROVIDE THE ENGINEERING REPORT LISTED BY
 UNIVERSAL ENGINEERING SCIENCES, DATED FEB. 07TH, 2022.
 2020 FBC-BUILDING 1803.5.2 QUESTIONABLE SOIL.
  
 3) SHEET S002 GENERAL NOTES:
 3A) WELDING. WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 3B) PLYWOOD ROOF SHEATHING NOTE LIST THE USE OF PLYWOOD
 ROOF SHEATHING. NOTE THIS IS A CONSTRUCTION TYPE LL-B
 BUILDING TYPE. THE 2020 FBC-BUILDING CODE SECTION
 603.1.1.3 FIRE RETARDANT TREATED WOOD SHALL BE
 PERMITTED IN ROOF CONSTRUCTION INCLUDING GIRDERS,
 FRAMING AND DECKING.
  
 4) SHEET A101:
 4A) THE FLOOR PLAN SHOWS TWO OUTSWING DOORS, IT APPEARS
 THAT THEY SWING OUT OVER THE PROPERTY LINE AND INTO THE
 RIGHT-OF-WAY. SEE SECTION 3202.2 2020 FBC-BUILDING
 CODE. SEE SURVEY IT APPEARS THE PROPERTY LINE IS THE
 FRONT OF THE BUILDING.
  
 4B) THE SAME ISSUE APPEARS WITH S2 THE STOREFRONT DOOR
 SYSTEM, THE PLAN DOES NOT INDICATE IF THE DOORS WILL
 FOLD OUT OVER THE PROPERTY LINE OR BACK INTO THE
 BUILDING, ADDITIONAL INFORMATION IS REQUIRED FOR CODE
 COMPLIANCE, 3202.2 2020 FBC-BUILDING CODE. SHEET A601
 DETAIL NOT HELPFUL. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) SHEET LS101 & LS102 THE 3 FEET WIDE EXIT DOORS ARE
 TAKING A CLEAR WIDTH OF 35 INCHES OR 178 OCCUPANTS.
 2020 ACCESS. CODE 404.2.3. CLEAR WIDTH & SIZE OF DOORS,
 2020 FBC-B 1010.1.1. THE MINIMUM SIZE OF A SWING DOORS
 IS MEASURED CLEAR OPENING OF THE DOORWAY WITH THE
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 34INCHES/ 0.20= 170 OCCUPANTS NOT THE 178. PLEASE
 ADDRESS CLEAR WIDTH OF ALL EGRESS DOORS.
  
 6) SHEET A401 FRONT & REAR ELEVATIONS. THE FRONT
 ELEVATION SHOWS THE CITY SIDEWALK RAMPED UP TO MEET
 YOUR NEW FINISH FLOOR LEVEL, IT APPEARS THE CITY
 SIDEWALK IS RAISED AND ADDITIONAL 6 INCHES AT THE NEW
 DOORWAYS, PLEASE PROVIDE WHY THIS OCCURS WITH A NEW
 CONSTRUCTION ON THE EAST AND WEST WALLS? 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 7) SHEET A301:
 7A) THE ROOF PLAN SHOWS THE USE OF A ROOF HATCH AND
 DETAIL TO GAIN ACCESS ONTO THE ROOF. THE ROOF HATCH
 SHOWS A CLEAR OPENING OF 3X3=9 SQ. FT. PLEASE REVIEW IN
 THE 2020 FBC-BUILD CODE SECTION 1011.12.2 ROOF ACCESS
 THE EXCEPTION, THE ROOF HATCH SHALL NOT BE LESS THAN 16
 SQ. FT. IN AREA AND HAVING A MINIMUM DIMENSION OF 2
 FEET.
  
 7B) ROOF OVERFLOW SCUPPERS ARE SHOWN DETAIL GIVEN
 5/A-303 BUT NEITHER PROVIDE THE MINIMUM WIDTH AND
 HEIGHT IN ACCORDANCE WITH 1503.4.1 THE SIZING AND
 INSTALLATION OF THE SECONDARY OVERFLOW IN ACCORDANCE
 WITH FBC-PLUMBING CODE CHAPTER 11.
  
 8) SHEET A502:
 8A) SHOWS A CUT SECTION THROUGH THE ELEVATOR SHAFT AND
 ELEVATOR PIT. THIS DETAIL SHOWS THE BOTTOM OF THE
 ELEVATOR PIT BOTTOM OF FOUNDATION BELOW 5 FEET BELOW
 FINISH FLOOR AND DEEPER POSSIBLY ANOTHER 2 FEET 6
 INCHES FOR THE BOTTOM GRADE FOR THE SUMP PIT. NOTE
 STATES THE GC SHALL HIRE A LICENSED SHORING ENGINEER TO
 TEMPORARY SUPPORT THE EXISTING WALL OF 905/ AND 915.
 SHOW COMPLIANCE WITH BOTH SECTIONS 1803.5.7 & 1804.2.1.
 THE UNDERPINNING SEQUENCE OF INSTALLATION SHALL BE
 IDENTIFIED AND INSTALLED IN ACCORDANCE WITH APPROVED
 CONSTRUCTION DOCUMENTS. 2020 FBC-BUILDING.
  
 8B) THE ELEVATOR SECTION SHOWS THE USE OF UNDERGROUND
 HYDRAULIC ELEVATOR CYLINDER. PLEASE PROVIDE COMPLIANCE
 WITH THE 2020 FBC-BUILDING CODE SECTION
 3011.1.1-3011.1.3.
  
 8C) SHEET A.502, NOR LS101 OR LS102 SHOW THE LOCATION
 OF THE ELEVATOR MACHINE ROOM MUST MEET THE REQUIREMENTS
 OF SECTION 3005.1-3005.6 IF APPLICABLE, 2020
 FBC-BUILDING CODE. MACHINE ROOMS CAN NOT BE IN THE
 LOBBY/ VESTIBULE.
  
 9) SHEET A601 WINDOW DETAILS DO NOT SHOW THE USE OF
 FLASHING IN ACCORDANCE TO SECTION 1405.4 OF THE: 2020
 FBC-BUILDING CODE SECTION 1405.4. FLASHINGS SHALL BE
 INSTALLED AT THE PERIMETERS OF EXTERIOR DOORS & WINDOW
 ASSEMBLIES. WHEN SELF-ADHERED MEMBRANES ARE USED AS
 FLASHINGS IN WALL ASSEMBLIES, THOSE SELF-ADHERED
 FLASHINGS SHALL COMPLY WITH AAMA-711.
  
 10) SHEET M-102 HAS A NOTE FOR THE A/C STAND FOR
 CONDENSERS NOA 17-1226.24. PLEASE NOTE THIS NOA HAS
 BEEN SUPERSEDED BY NOA18-0828.09.
  
 10A) ROOF TOP A/C STANDS MUST ALSO MEET THE MINIMUM
 HEIGHT REQUIREMENTS FOUND IN TABLE 1510.10 OF THE 2020
 FBC-BUILDING CODE. HEIGHT OF THE STAND SHOULD BE
 MEASURED TO THE BOTTOM OF THE LOWEST HORIZONTAL FRAMING
 MEMBER OF THE STAND AND THE HEIGHT OF THE STAND DEPENDS
 ON THE WIDTH OF THE MECHANICAL UNIT.
  
 10B) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 10C) FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C
 STANDS, AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF
 FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND
 TO THE EQUIPMENT ABOVE.
  
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 11) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  