2023-01-10 07:58:06 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22120561 |
| ADD: 915 N. RAILROAD AVE. |
| CONT: HEDRICK BROTHERS CONSTRRUCTION |
| TEL: 561-308-2954 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JAN. 04TH/2023 |
| ACTION: DENIED |
| |
| 1) SHEET T100 TITLE SHEET: |
| 1A) PROJECT DESCRIPTION THE EXISTING BUILDING IS |
| DEMOLISHED WITH EXCEPTION OF THE NORTH AND OR SOUTH |
| WALLS TO REMAIN. NEW BUILDING IS PROPOSED IN ITS PLACE. |
| 2020 EXISTING BUILDING CODE SECTION 907.4.1. |
| (ALTERATION LEVEL LLL ALTERATION) EVALUATION AND |
| ANALYSIS. AN ENGINEERING EVALUATION AND ANALYSIS THAT |
| ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED |
| STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN |
| PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. HOW |
| WILL THE 2 STORY SIDE WALLS AND FOOTER BE KEPT FROM |
| OVERTURNING DURING CONSTRUCTION. EVERY STRUCTURE SHALL |
| BE DESIGNED TO RESIST THE OVERTURNING POSITIVE & |
| NEGATIVE EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED |
| IN THIS CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| |
| 1B) 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL |
| NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1C) BUILDING PROVISO: DEFERRED SUBMITTALS: |
| COMPONENTS & CLADDING. |
| (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: CURTAINWALL, STOREFRONTS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP VENTILATORS |
| (E) PRE-ENGINEERED ROOFTOP A/C STANDS |
| STAIR & ELEVATOR SHOP DRAWINGS |
| ROOF ACCESS LADDER SHOP DRAWINGS |
| FRONT CANOPY SHOP DRAWINGS |
| STEEL SHOP DRAWINGS |
| |
| 1D) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF |
| APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 1E) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. |
| PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE AND |
| SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| USED IN THE TESTS. |
| |
| |
| 2) SHEET S001 GENERAL NOTES: GEOTECHNICAL INVESTIGATIVE |
| REPORT. PLEASE PROVIDE THE ENGINEERING REPORT LISTED BY |
| UNIVERSAL ENGINEERING SCIENCES, DATED FEB. 07TH, 2022. |
| 2020 FBC-BUILDING 1803.5.2 QUESTIONABLE SOIL. |
| |
| 3) SHEET S002 GENERAL NOTES: |
| 3A) WELDING. WELDED OR BOLTED CONNECTIONS. THIS |
| BUILDING CONTAINS EITHER BOLTED AND OR WELDED |
| CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| BE REQUIRED. |
| THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| INSPECTION. |
| 2020 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD |
| BRUNELLE AT 561-805-6670. |
| |
| 3B) PLYWOOD ROOF SHEATHING NOTE LIST THE USE OF PLYWOOD |
| ROOF SHEATHING. NOTE THIS IS A CONSTRUCTION TYPE LL-B |
| BUILDING TYPE. THE 2020 FBC-BUILDING CODE SECTION |
| 603.1.1.3 FIRE RETARDANT TREATED WOOD SHALL BE |
| PERMITTED IN ROOF CONSTRUCTION INCLUDING GIRDERS, |
| FRAMING AND DECKING. |
| |
| 4) SHEET A101: |
| 4A) THE FLOOR PLAN SHOWS TWO OUTSWING DOORS, IT APPEARS |
| THAT THEY SWING OUT OVER THE PROPERTY LINE AND INTO THE |
| RIGHT-OF-WAY. SEE SECTION 3202.2 2020 FBC-BUILDING |
| CODE. SEE SURVEY IT APPEARS THE PROPERTY LINE IS THE |
| FRONT OF THE BUILDING. |
| |
| 4B) THE SAME ISSUE APPEARS WITH S2 THE STOREFRONT DOOR |
| SYSTEM, THE PLAN DOES NOT INDICATE IF THE DOORS WILL |
| FOLD OUT OVER THE PROPERTY LINE OR BACK INTO THE |
| BUILDING, ADDITIONAL INFORMATION IS REQUIRED FOR CODE |
| COMPLIANCE, 3202.2 2020 FBC-BUILDING CODE. SHEET A601 |
| DETAIL NOT HELPFUL. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 5) SHEET LS101 & LS102 THE 3 FEET WIDE EXIT DOORS ARE |
| TAKING A CLEAR WIDTH OF 35 INCHES OR 178 OCCUPANTS. |
| 2020 ACCESS. CODE 404.2.3. CLEAR WIDTH & SIZE OF DOORS, |
| 2020 FBC-B 1010.1.1. THE MINIMUM SIZE OF A SWING DOORS |
| IS MEASURED CLEAR OPENING OF THE DOORWAY WITH THE |
| SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| 34INCHES/ 0.20= 170 OCCUPANTS NOT THE 178. PLEASE |
| ADDRESS CLEAR WIDTH OF ALL EGRESS DOORS. |
| |
| 6) SHEET A401 FRONT & REAR ELEVATIONS. THE FRONT |
| ELEVATION SHOWS THE CITY SIDEWALK RAMPED UP TO MEET |
| YOUR NEW FINISH FLOOR LEVEL, IT APPEARS THE CITY |
| SIDEWALK IS RAISED AND ADDITIONAL 6 INCHES AT THE NEW |
| DOORWAYS, PLEASE PROVIDE WHY THIS OCCURS WITH A NEW |
| CONSTRUCTION ON THE EAST AND WEST WALLS? 2020 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION 107.2.1. |
| CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 7) SHEET A301: |
| 7A) THE ROOF PLAN SHOWS THE USE OF A ROOF HATCH AND |
| DETAIL TO GAIN ACCESS ONTO THE ROOF. THE ROOF HATCH |
| SHOWS A CLEAR OPENING OF 3X3=9 SQ. FT. PLEASE REVIEW IN |
| THE 2020 FBC-BUILD CODE SECTION 1011.12.2 ROOF ACCESS |
| THE EXCEPTION, THE ROOF HATCH SHALL NOT BE LESS THAN 16 |
| SQ. FT. IN AREA AND HAVING A MINIMUM DIMENSION OF 2 |
| FEET. |
| |
| 7B) ROOF OVERFLOW SCUPPERS ARE SHOWN DETAIL GIVEN |
| 5/A-303 BUT NEITHER PROVIDE THE MINIMUM WIDTH AND |
| HEIGHT IN ACCORDANCE WITH 1503.4.1 THE SIZING AND |
| INSTALLATION OF THE SECONDARY OVERFLOW IN ACCORDANCE |
| WITH FBC-PLUMBING CODE CHAPTER 11. |
| |
| 8) SHEET A502: |
| 8A) SHOWS A CUT SECTION THROUGH THE ELEVATOR SHAFT AND |
| ELEVATOR PIT. THIS DETAIL SHOWS THE BOTTOM OF THE |
| ELEVATOR PIT BOTTOM OF FOUNDATION BELOW 5 FEET BELOW |
| FINISH FLOOR AND DEEPER POSSIBLY ANOTHER 2 FEET 6 |
| INCHES FOR THE BOTTOM GRADE FOR THE SUMP PIT. NOTE |
| STATES THE GC SHALL HIRE A LICENSED SHORING ENGINEER TO |
| TEMPORARY SUPPORT THE EXISTING WALL OF 905/ AND 915. |
| SHOW COMPLIANCE WITH BOTH SECTIONS 1803.5.7 & 1804.2.1. |
| THE UNDERPINNING SEQUENCE OF INSTALLATION SHALL BE |
| IDENTIFIED AND INSTALLED IN ACCORDANCE WITH APPROVED |
| CONSTRUCTION DOCUMENTS. 2020 FBC-BUILDING. |
| |
| 8B) THE ELEVATOR SECTION SHOWS THE USE OF UNDERGROUND |
| HYDRAULIC ELEVATOR CYLINDER. PLEASE PROVIDE COMPLIANCE |
| WITH THE 2020 FBC-BUILDING CODE SECTION |
| 3011.1.1-3011.1.3. |
| |
| 8C) SHEET A.502, NOR LS101 OR LS102 SHOW THE LOCATION |
| OF THE ELEVATOR MACHINE ROOM MUST MEET THE REQUIREMENTS |
| OF SECTION 3005.1-3005.6 IF APPLICABLE, 2020 |
| FBC-BUILDING CODE. MACHINE ROOMS CAN NOT BE IN THE |
| LOBBY/ VESTIBULE. |
| |
| 9) SHEET A601 WINDOW DETAILS DO NOT SHOW THE USE OF |
| FLASHING IN ACCORDANCE TO SECTION 1405.4 OF THE: 2020 |
| FBC-BUILDING CODE SECTION 1405.4. FLASHINGS SHALL BE |
| INSTALLED AT THE PERIMETERS OF EXTERIOR DOORS & WINDOW |
| ASSEMBLIES. WHEN SELF-ADHERED MEMBRANES ARE USED AS |
| FLASHINGS IN WALL ASSEMBLIES, THOSE SELF-ADHERED |
| FLASHINGS SHALL COMPLY WITH AAMA-711. |
| |
| 10) SHEET M-102 HAS A NOTE FOR THE A/C STAND FOR |
| CONDENSERS NOA 17-1226.24. PLEASE NOTE THIS NOA HAS |
| BEEN SUPERSEDED BY NOA18-0828.09. |
| |
| 10A) ROOF TOP A/C STANDS MUST ALSO MEET THE MINIMUM |
| HEIGHT REQUIREMENTS FOUND IN TABLE 1510.10 OF THE 2020 |
| FBC-BUILDING CODE. HEIGHT OF THE STAND SHOULD BE |
| MEASURED TO THE BOTTOM OF THE LOWEST HORIZONTAL FRAMING |
| MEMBER OF THE STAND AND THE HEIGHT OF THE STAND DEPENDS |
| ON THE WIDTH OF THE MECHANICAL UNIT. |
| |
| 10B) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| |
| 10C) FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C |
| STANDS, AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF |
| FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND |
| TO THE EQUIPMENT ABOVE. |
| |
| 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 11) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT |
| REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |