2023-01-12 18:10:16 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22120553 |
| 255 EVERNIA ST # 204 |
| |
| NOTE: |
| LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| THE FLORIDA BUILDING CODE. |
| |
| (1)-FLOORING SOUND INSULATION MATERIAL: |
| (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| (2020). |
| |
| (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| |
| NOTE: |
| SOUND INSULATION TEST SUBMITTED IS FOR A CONCRETE SLAB |
| WITH A SUSPENDED ACOUSTICAL CEILING. THIS TEST DOESN'T |
| MATCH BUILDING ACTUAL CONDITIONS. THERE IS NO |
| ACOUSTICAL CEILING IN THIS BUILDING. NEED TO PROVIDE |
| COPY OF TEST FOR CONCRETE SLAB WITHOUT ACOUSTICAL |
| CEILING. |
| |
| (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| |
| NOTE: |
| SOUND INSULATION TEST SUBMITTED IS FOR A CONCRETE SLAB |
| WITH A SUSPENDED ACOUSTICAL CEILING. THIS TEST DOESN'T |
| MATCH BUILDING ACTUAL CONDITIONS. THERE IS NO |
| ACOUSTICAL CEILING IN THIS BUILDING. NEED TO PROVIDE |
| COPY OF TEST FOR CONCRETE SLAB WITHOUT ACOUSTICAL |
| CEILING. |
| |
| NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| (2)PROVIDE FLOOR PLAN OR SKETCH OF APARTMENT SHOWING |
| AREAS OF WORK. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |