2023-03-01 11:13:06 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) RESOLVED. HOWEVER DIGITAL SIGNATURE IS NOT APPROVED. | | | | 2) RESOLVED. | | | | 3) NOT RESOLVED. [PROVIDE A NOTE FOR THIS ON THE | | SURVEY.] THE GENERATOR EXHAUST IS REQUIRED TO BE AT | | LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | |
|