2023-01-26 09:21:02 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | GENERATOR. FBC AMENDMENTS 107.2.1 | | | | 2) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD | | ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD | | WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC | | ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1 | | | | 3) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | PARKING LOTS AND LOADING DOCKS. | | |
|