2022-12-28 13:58:23 | ELECTRIC REVIEW FAILED |
| 1) ELECTRIC PANEL LOCATION DOES NOT COMPLY WITH NEC |
| 110.26 CLEARANCES |
| 2) ELECTRIC PLAN INDICATES VARIOUS ELECTRICAL |
| RECEPTACLES, PLEASE INDICATE WHETHER THESE ARE |
| EXISTING, NEW, MODIFIED OR REPLACED. FBC 107.2 |
| 3) PLEASE DETAIL NEW KITCHEN LIGHTS AND OTHER WIRING TO |
| BE ARC FAULT PROTECTED. NEC 210.12 |
| 4) PLEASE PROVIDE A PANEL SCHEDULE INDICATING ALL THE |
| REQUIRED CIRCUITS AS PER NEC 210.11 |
| 5) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, |
| OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR |
| PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |