Plan Review Notes
Plan Review Notes For Permit 22120545
Permit Number 22120545
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-28 13:58:23ELECTRIC REVIEW FAILED
 1) ELECTRIC PANEL LOCATION DOES NOT COMPLY WITH NEC
 110.26 CLEARANCES
 2) ELECTRIC PLAN INDICATES VARIOUS ELECTRICAL
 RECEPTACLES, PLEASE INDICATE WHETHER THESE ARE
 EXISTING, NEW, MODIFIED OR REPLACED. FBC 107.2
 3) PLEASE DETAIL NEW KITCHEN LIGHTS AND OTHER WIRING TO
 BE ARC FAULT PROTECTED. NEC 210.12
 4) PLEASE PROVIDE A PANEL SCHEDULE INDICATING ALL THE
 REQUIRED CIRCUITS AS PER NEC 210.11
 5) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  