Plan Review Notes For Permit 22120505 |
Permit Number |
22120505 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-12 09:37:54 | FIRE REVIEW COMMENTS: | | | | (1) PROVIDE THE DIMENSIONS OF THE PROPOSED KITCHEN | | TENT. NFPA 1, 1.14 | | | | (2) PROVIDE THE DISTANCE OF THE GENERATORS TO THE | | KITCHEN TENT. NFPA 1, 1.14 | | | | (3) WILL ANY COOKING OPERATIONS BE TAKING PLACE UNDER A | | TENT. NFPA 10.10.6 | | | | (4) PROVIDE A FLAME CERTIFICATE FOR THE TENT MATERIAL. | | NFPA 101, 11.11.2.2 | | | | (5) PROVIDE PORTABLE FIRE EXTINGUISHER UNDER TENT. NFPA | | 101, 11.11.5 | | | | | | (6) PROVIDE ???NO SMOKING??? SIGNAGE UNDER TENT. | | | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|