Plan Review Notes
Plan Review Notes For Permit 22120421
Permit Number 22120421
Review Stop G
Sequence Number 1
Notes
Date Text
2022-12-16 14:50:531ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22120421
 12/16/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: SHOW THE DIAMETER OF THE SUPPLY PIPE FROM
 THE METER TO THE FIRST TEE. BASED ON THE 888,000 BTU
 LOAD SHOWN, A 1-INCH DIAMETER SCHEDULE 40 PIPE IS
 REQUIRED- TABLE 402.4(5) FBC FG.
  
 2) GAS RISER: SHOW THE DIAMETER OF THE SCHEDULE 40 PIPE
 FROM THE 2LB. REG. TO THE TEE FOR THE INTERIOR RUN.
 BASED ON TABLE 402.4(3) A 3/4-INCH PIPE IS REQUIRED.
  
 3) SURVEY: IT APPEARS THE TANKLESS WATER HEATER IS
 WITHIN 4 FT. OF THE BATHROOM WINDOW. PLEASE VERIFY THE
 WINDOW IS NON-OPERABLE OR RELOCATE THE UNIT- SEC.
 G2427.8 FBC RES.
  
 4) SURVEY: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED
 TO THE RANGE AND PROVIDE CALCULATIONS- SEC. G2407.1 FBC
 RES.
  
 5) GAS RISER AND SURVEY: A SEPARATE PERMIT IS REQUIRED
 FOR THE POOL HEATER. PLEASE LABEL IT AS FUTURE ON THE
 PLANS AND PROVIDE A GAS-TIGHT CAP- SEC. 105.1 WPB, AND
 SEC. G2415.15 FBC RES.
  
 5) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL
 BE ON THE GAS RISER AND THE MARKED UP SURVEY- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  