Date |
Text |
2022-12-20 14:40:53 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II/INSPECTOR |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| DEMO PERMIT PER FLORIDA BUILDING |
| CODE, BUILDING 3303: |
| |
| NOTE: PLEASE PROVIDE INFORMATION FOR EACH ITEM BELOW: |
| |
| 1. PROVIDE ELECTRIC PERMIT TO ENSURE THAT ALL |
| ELECTRICITY HAS BEEN DISCONNECTED (INCLUDING ANY POWER |
| POLES/SIGNS) AND CONFIRM THAT SITE IS SAFE. |
| |
| 3. WATERDOWN METHOD: |
| IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED |
| INFPRMATION OF THE WATER TRUCK SUCH AS: THE |
| GALLON CAPACITY OF THE WATER TANK AND A LETTER |
| INCLUDING A STATEMENT THAT THE WATER |
| USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY |
| AND WILL BE ON-SITE AT ALL TIMES |
| DURING DEMOLITION. |
| IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| THEN A PARTIAL RELEASE WILL BE NOTED |
| ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS |
| SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE |
| SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE |
| BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY |
| THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE |
| COMPLETED "DEMOLITION APPLICATION" FORM TO |
| 561-822-2183. |
| |
| 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART |
| MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS |
| IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR |
| THE FORM TO [email protected]. |
| |
| |