2023-01-05 11:50:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE APPEARS TO BE AN INDICATION OF THE FACP BEING |
| LOCATED IN THE SOUTH BUILDING. |
| |
| THERE DOES NOT APPEAR TO BE ANY INDICATION OF A SISTER |
| PANEL NOR ANNUCIATOR PANEL AT THIS NORTH BUILDING. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.4.3.2 ANNUNCIATION, AND ANNUNCIATION ZONING, IN |
| ACCORDANCE WITH |
| 9.6.7 SHALL BE PROVIDED, UNLESS THE BUILDING COMPLIES |
| WITH EITHER |
| 30.3.4.3.3 OR 30.3.4.3.4. ANNUNCIATION SHALL BE |
| PROVIDED AT A LOCATION |
| READILY ACCESSIBLE FROM THE PRIMARY POINT OF ENTRY FOR |
| EMERGENCY |
| RESPONSE PERSONNEL |
| |
| 9.6.7.7 WHERE THE SYSTEM SERVES MORE THAN ONE BUILDING, |
| EACH BUILDING |
| SHALL BE ANNUNCIATED SEPARATELY |
| |
| PLEASE REVIEW AND CORRECT. COORDINATE THE PANEL THROUGH |
| THE OFFICE OF THE FIRE MARSHAL BY EMAIL NOTED BELOW |
| THRU PDF WITH PROPOSED LOCATIONS. |
| |
| |
| |
| 2) THERE APPEARS TO BE AN INDICATION OF THE FACP BEING |
| LOCATED IN THE SOUTH BUILDING. |
| |
| THE CALCULATIONS DO NOT APPEAR TO INDICATE THE SIZE AND |
| LENGHT OF WIRE FROM THE SOUTH BLDG. |
| |
| PLEASE REVIEW AND PROVIDE CLARIFICATION AND |
| CONFIRMATION AND OR CORRECT. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |