2023-01-05 08:49:45FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E1.1
  
 301 WEST MLO PANEL NEEDS TO TERMINATE IN A SINGLE
 OVERCURRENT DEVICE PER 240.21 BOTH THE 10' AND 25'
 RULES TERMINATE IN A SINGLE OCP DEVICE.
  
 PLEASE LABEL ALL MAINS ON PLANS FOR BOTH SERVICES.
  
 PAGE E2.1
  
 BATHROOMS ARE SHOWN OVER THE MAIN SWITCH GEAR ROOM
 PLEASE BE CAREFUL NOT TO LOCATE AND DRAINS OR SUPPLIES
 OVER THE GEAR BELOW. 110.26(E)
  
  