Plan Review Notes
Plan Review Notes For Permit 22120118
Permit Number 22120118
Review Stop B
Sequence Number 1
Notes
Date Text
2022-12-20 16:09:52NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS,DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 2) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE PER
 FBC R807.1
  
 3) DRAWING 01 - FLOOR PLAN - BEDROOM NUMBER 2 SHOWS THE
 EGRESS WINDOW DESIGNATION AS A AND B - WHICH DOES NOT
 MEET THE EMERGENCY EGRESS REQUIREMENT - FBC R310.2
  
 4) PLEASE PROVIDE A SITE PLAN THAT SHOWS THE STORM
 WATER DRAINAGE FLOW AWAY FROM THE BUILDING AND AWAY
 FROM THE NEIGHBORING PROPERTY - FBC WPB 107.2.5 SITE
 PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)