Date |
Text |
2022-12-13 08:51:12 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL1654-R30 SYSTEM NO. W-146 DOES NOT MEET THE |
| MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED SYSTEM |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL27499.1-R4 SELECTED OPTION #1 MAXIMUM DESIGN |
| PRESSURE -116 PSF. DO NOT MEET THE MINIMUM ZONE 3 |
| DESIGN PRESSURE REQUIREMENT OF -121 FOR EXPOSURE |
| CATEGORY C AREAS WITH A GABLE ROOF; ROOF SLOPES |
| 2/12-4/12 MEAN ROOF HEIGHT UP TO 15 FT. SELECT OPTION |
| THAT MEETS OR EXCEEDS THIS REQUIREMENT. ALL APPLICABLE |
| DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS |
| NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. |
| 3. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF |
| DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW |
| SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD |
| OF PROVIDING POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |