Plan Review Notes
Plan Review Notes For Permit 22120022
Permit Number 22120022
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2023-01-30 10:37:561. GENERAL NOTE 9 IN ENGINEERING STATES THIS IS NOT
 SITE SPECIFIC. THIS PROJECT REQUIRES SITE SPECIFIC
 ENGINEERED DESIGN PRESSURES. FBC 107.1 2. SUBMITTED
 DESIGN PRESSURE FOR UNITS 3A, 3B, AND 3C REQUIRE
 -110.9. FBC/NOA SUBMISSION IS TESTED AT -110.0, AND
 DOES NOT COMPLY. FBC 107.2. 3. PLEASE PROVIDE A
 FLASHING DETAIL, OR ADD A NOTE TO THE PLAN,
 DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC B
 1405.4.