Plan Review Notes For Permit 22120007 |
Permit Number |
22120007 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-04 18:02:52 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22120007 | | 1/4/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P-100: PLEASE PROVIDE A STORM DRAIN ISOMETRIC | | DRAWING THAT SHOWS THE ANTICIPATED GPM FLOW AT EACH | | DRAIN LOCATION AND ACCUMULATIVE GPM FLOW AT POINTS OF | | CONNECTION TO EXISTING MAINS- SEC. 107.3.5.1.3 (14) WPB | | & SEC. 1106.2 FBC P. | | | | 2) P-100: PLEASE PROVIDE MORE INFORMATION ABOUT THE | | VACUUM PUMP. CLARIFY THE PURPOSE OF THE PUMP AND WHAT | | IT???S FUNCTION WILL BE. WILL IT BE A PERMANENT | | INSTALLATION OR PORTABLE? PLEASE PROVIDE AN EQUIPMENT | | SCHEDULE ON THE PLAN- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|