2023-01-04 18:02:521ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22120007
 1/4/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-100: PLEASE PROVIDE A STORM DRAIN ISOMETRIC
 DRAWING THAT SHOWS THE ANTICIPATED GPM FLOW AT EACH
 DRAIN LOCATION AND ACCUMULATIVE GPM FLOW AT POINTS OF
 CONNECTION TO EXISTING MAINS- SEC. 107.3.5.1.3 (14) WPB
 & SEC. 1106.2 FBC P.
  
 2) P-100: PLEASE PROVIDE MORE INFORMATION ABOUT THE
 VACUUM PUMP. CLARIFY THE PURPOSE OF THE PUMP AND WHAT
 IT???S FUNCTION WILL BE. WILL IT BE A PERMANENT
 INSTALLATION OR PORTABLE? PLEASE PROVIDE AN EQUIPMENT
 SCHEDULE ON THE PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  