Plan Review Notes
Plan Review Notes For Permit 22111270
Permit Number 22111270
Review Stop M
Sequence Number 3
Notes
Date Text
2023-02-27 10:59:003RD REVIEW FMC
 PERMIT: 22111270
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANT DENSITY OF FMC TABLE 403.3.1.1 FOR THE LOBBY.
 THE CORRECTED OCCUPANT COUNT WOULD BE 25 OCCUPANTS.
  
 ALL OF THE OTHER DUCTWORK AND OPENINGS WILL NOT BE
 REVIEWED UNTIL THE UPFIT FOR THE SPACE IS SUBMITTED FOR
 REVIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  