Plan Review Notes
Plan Review Notes For Permit 22111270
Permit Number 22111270
Review Stop P
Sequence Number 2
Notes
Date Text
2023-02-17 14:34:51 
 2ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22111270
 2/17/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P.001, P.100, P.101, P.102, & P.700 SHOWN IN
 THE INDEX ON SHEET T.100 WERE NOT UPLIOADED FOR REVIEW.
 SHEETS P.102 & P.701 WHICH ARE REFERENCED IN THE
 RESPONSE TO COMMENTS NARRATIVE BY CES ENGINEERING WERE
 ALSO NOT UPLOADED. A THOROUGH PLUMBING REVIEW CANNOT BE
 COMPLETED WITHOUT A FULL SET OF PLUMBING PLANS- SEC.
 107.2.1 WPB. PLEASE REVIEW REMAINING COMMENTS 1, 2, & 4
 FROM THE FIRST REVIEW COPIED BELOW.
  
 2) P.500: THE NEW INSTA-HOT WATER HEATER WILL REQUIRE
 AN ASSE APPROVED MIXING VALVE TO LIMIT THE HOT WATER
 TEMPERATURE DELIVERY FROM THE MOP SINK- SEC. 607.1.1
 FBC P.
  
 1ST REVIEW COMMENTS BELOW.
  
 1) SHEETS A.101 & A.502: THE DRAWINGS SHOW AN ELEVATOR
 SUMP PIT. ASSUMING THE PIT IS FOR A HYDRAULIC ELEVATOR
 PLEASE DETAIL THE SUMP PUMP INSTALLATION INCLUDING SUMP
 PIT DIMENSIONS AND PUMP PIPING CONNECTIONS AND DRAINAGE
 DISCHARGE LOCATION- SECS. 712.3- 712.3.5 FBC P. PLEASE
 INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP AND NOTE AN
 OIL INTERCEPTOR IS REQUIRED FOR THE PUMP DRAINAGE
 SYSTEM UNLESS THE PUMP IS EQUIPPED WITH AN APPROVED
 ALARM SYSTEM- SEC. 1003.4 FBC P.
  
 2) A.102: PROVIDE SANITARY AND WATER RISER DRAWINGS FOR
 INSTALLATION OF THE NEW MOP SINK- SEC. 107.3.5.1.3 FBC
 P. PLEASE INCLUDE A LAYOUT PLAN THAT SHOWS THE LOCATION
 OF THE NEW DRAIN LINE CONNECTION TO THE EXISTING
 BUILDING DRAIN.
  
 4) A.301 PROVIDE ROOF DRAINAGE CALCULATIONS INCLUDING
 THE RAIN FALL RATE, DRAINAGE SQUARE FOOTAGE INCLUDING
 PARAPET WALLS, TOTAL GPM FLOW, AND GPM FLOW AT EACH
 PRIMARY AND SECONDARY DRAIN LOCATION- SEC. 1106.1 &
 1106.2 FBC P.
 A) PROVIDE A STORM DRAIN ISOMETRIC DRAWING SHOWING
 VERTICAL LEADER AND HORIZONTAL DRAIN SIZES, AND
 DISCHARGE LOCATIONS- SEC. 1101.2, 1106.1, 1106.2 &
 1106.3 FBC P.
 B) SHOW THE DIMENSIONS OF THE NEW SCUPPER REPLACEMENTS-
 SEC. 1106.5 & 1108.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  