2022-12-09 14:06:59 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22111270 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A.101 & A.502: THE DRAWINGS SHOW AN ELEVATOR |
| SUMP PIT. ASSUMING THE PIT IS FOR A HYDRAULIC ELEVATOR |
| PLEASE DETAIL THE SUMP PUMP INSTALLATION INCLUDING SUMP |
| PIT DIMENSIONS AND PUMP PIPING CONNECTIONS AND DRAINAGE |
| DISCHARGE LOCATION- SECS. 712.3- 712.3.5 FBC P. PLEASE |
| INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP AND NOTE AN |
| OIL INTERCEPTOR IS REQUIRED FOR THE PUMP DRAINAGE |
| SYSTEM UNLESS THE PUMP IS EQUIPPED WITH AN APPROVED |
| ALARM SYSTEM- SEC. 1003.4 FBC P. |
| |
| 2) A.102: PROVIDE SANITARY AND WATER RISER DRAWINGS FOR |
| INSTALLATION OF THE NEW MOP SINK- SEC. 107.3.5.1.3 FBC |
| P. PLEASE INCLUDE A LAYOUT PLAN THAT SHOWS THE LOCATION |
| OF THE NEW DRAIN LINE CONNECTION TO THE EXISTING |
| BUILDING DRAIN. |
| |
| 3) A.102: SHOW THE SOURCE OF THE HOT WATER FOR THE MOP |
| SINK- SEC. 607.1 FBC P. IF A NEW WATER HEATER IS |
| PROPOSED PLEASE SHOW THE LOCATION AND PROVIDE THE |
| FOLLOWING INFORMATION: |
| A) EQUIPMENT SCHEDULE. |
| B) PROVIDE A SCHEMATIC DRAWING THAT SHOWS PIPING |
| CONNECTIONS INCLUDING THE COLD WATER FEED, CHECK VALVE, |
| HOT WATER SUPPLY, THERMAL EXPANSION CONTROL, HOT WATER |
| RECIRCULATION PUMP (IF INSTALLED), AND MASTER |
| THERMOSTATIC MIXING VALVE- SECS. 607.1.1, 607.2.2, |
| 607.3 FBC P. |
| C) PROVIDE RELIEF VALVE PIPING DETAILS INCLUDING TYPE |
| AND SIZE OF RELIEF PIPE AND DISCHARGE LOCATION; PAN AND |
| PAN DRAIN DETAILS, PAN DRAIN RUN AND TERMINATION |
| LOCATION- SECS. 504.4- 504.7.2 FBC P. |
| |
| 4) A.301 PROVIDE ROOF DRAINAGE CALCULATIONS INCLUDING |
| THE RAIN FALL RATE, DRAINAGE SQUARE FOOTAGE INCLUDING |
| PARAPET WALLS, TOTAL GPM FLOW, AND GPM FLOW AT EACH |
| PRIMARY AND SECONDARY DRAIN LOCATION- SEC. 1106.1 & |
| 1106.2 FBC P. |
| A) PROVIDE A STORM DRAIN ISOMETRIC DRAWING SHOWING |
| VERTICAL LEADER AND HORIZONTAL DRAIN SIZES, AND |
| DISCHARGE LOCATIONS- SEC. 1101.2, 1106.1, 1106.2 & |
| 1106.3 FBC P. |
| B) SHOW THE DIMENSIONS OF THE NEW SCUPPER REPLACEMENTS- |
| SEC. 1106.5 & 1108.3 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |