Plan Review Notes
Plan Review Notes For Permit 22111270
Permit Number 22111270
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-09 14:06:591ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22111270
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A.101 & A.502: THE DRAWINGS SHOW AN ELEVATOR
 SUMP PIT. ASSUMING THE PIT IS FOR A HYDRAULIC ELEVATOR
 PLEASE DETAIL THE SUMP PUMP INSTALLATION INCLUDING SUMP
 PIT DIMENSIONS AND PUMP PIPING CONNECTIONS AND DRAINAGE
 DISCHARGE LOCATION- SECS. 712.3- 712.3.5 FBC P. PLEASE
 INCLUDE AN EQUIPMENT SCHEDULE FOR THE PUMP AND NOTE AN
 OIL INTERCEPTOR IS REQUIRED FOR THE PUMP DRAINAGE
 SYSTEM UNLESS THE PUMP IS EQUIPPED WITH AN APPROVED
 ALARM SYSTEM- SEC. 1003.4 FBC P.
  
 2) A.102: PROVIDE SANITARY AND WATER RISER DRAWINGS FOR
 INSTALLATION OF THE NEW MOP SINK- SEC. 107.3.5.1.3 FBC
 P. PLEASE INCLUDE A LAYOUT PLAN THAT SHOWS THE LOCATION
 OF THE NEW DRAIN LINE CONNECTION TO THE EXISTING
 BUILDING DRAIN.
  
 3) A.102: SHOW THE SOURCE OF THE HOT WATER FOR THE MOP
 SINK- SEC. 607.1 FBC P. IF A NEW WATER HEATER IS
 PROPOSED PLEASE SHOW THE LOCATION AND PROVIDE THE
 FOLLOWING INFORMATION:
 A) EQUIPMENT SCHEDULE.
 B) PROVIDE A SCHEMATIC DRAWING THAT SHOWS PIPING
 CONNECTIONS INCLUDING THE COLD WATER FEED, CHECK VALVE,
 HOT WATER SUPPLY, THERMAL EXPANSION CONTROL, HOT WATER
 RECIRCULATION PUMP (IF INSTALLED), AND MASTER
 THERMOSTATIC MIXING VALVE- SECS. 607.1.1, 607.2.2,
 607.3 FBC P.
 C) PROVIDE RELIEF VALVE PIPING DETAILS INCLUDING TYPE
 AND SIZE OF RELIEF PIPE AND DISCHARGE LOCATION; PAN AND
 PAN DRAIN DETAILS, PAN DRAIN RUN AND TERMINATION
 LOCATION- SECS. 504.4- 504.7.2 FBC P.
  
 4) A.301 PROVIDE ROOF DRAINAGE CALCULATIONS INCLUDING
 THE RAIN FALL RATE, DRAINAGE SQUARE FOOTAGE INCLUDING
 PARAPET WALLS, TOTAL GPM FLOW, AND GPM FLOW AT EACH
 PRIMARY AND SECONDARY DRAIN LOCATION- SEC. 1106.1 &
 1106.2 FBC P.
 A) PROVIDE A STORM DRAIN ISOMETRIC DRAWING SHOWING
 VERTICAL LEADER AND HORIZONTAL DRAIN SIZES, AND
 DISCHARGE LOCATIONS- SEC. 1101.2, 1106.1, 1106.2 &
 1106.3 FBC P.
 B) SHOW THE DIMENSIONS OF THE NEW SCUPPER REPLACEMENTS-
 SEC. 1106.5 & 1108.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  