2022-12-09 10:33:01 | RENOVATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR DOORS, WINDOWS AND |
| ROOFING SYSTEM. ALL PRODUCT APPROVALS NEED TO BE |
| REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| FBC WPB 107.3.4 |
| |
| 2) PLEASE SHOW THE ROOF SCUTTLE DISTANCE FROM EDGE OF |
| ROOF OR GUARD RAILS PER FBC 1015.7 ROOF ACCESS. |
| GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE |
| CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| INCHES (533 MM) IN DIAMETER. |
| |
| 3) PLEASE SHOW THE ROOF TOP EQUIPMENT DISTANCE FROM THE |
| EDGE OF THE ROOF - FBC 1015.6 MECHANICAL EQUIPMENT, |
| SYSTEMS AND DEVICES. |
| GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT |
| REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND |
| EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE |
| CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| INCHES (533 MM) IN DIAMETER. |
| |
| 4) EXTERIOR DOORS ON THE SOUTH AND EAST SIDE OF THE |
| BUILDING SHOULD NOT OPEN ON TO THE SIDE WALK - FBC |
| 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO |
| THE PUBLIC RIGHT-OF-WAY. |
| |
| 5) NOT A COMPLETE REVIEW -THE STRUCTURAL DRAWINGS ARE |
| NOT IN PROJECTDOX. |
| |