Plan Review Notes
Plan Review Notes For Permit 22111219
Permit Number 22111219
Review Stop B
Sequence Number 3
Notes
Date Text
2023-03-22 14:06:16JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R37
 COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2
 MECHANICALLY-ATTACHED BASE SHEET TABLE 4B ALLOWABLE
 DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE
 ROOF APPLICATIONS SYSTEM NO. UDL-39 DO NOT MEET OR
 EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENTS FOR A
 HIP ROOF; (3:12 AND OVER) ROOF SLOPE; MEAN ROOF HEIGHT
 30 FT. MINIMUM DESIGN PRESSURE REQUIREMENT OF -133.1 IN
 AN EXPOSURE CATEGORY C AREA. PROVIDE UNDERLAYMENT
 SYSTEM THAT MEETS OR EXCEEDS THE ABOVE CRITERIA. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved