Date |
Text |
2022-12-20 12:19:40 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL22525-R6 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). |
| 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R36 |
| HAS BEEN REVISED TO FL5259-R37. PLEASE PROVIDE A |
| COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS |
| MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE |
| UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE |
| SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS |
| FROM EACH CATEGORY TO BE USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. |
| 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R36 |
| (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| CONSIDER USING FL5259-R37 (NON-HVHZ). |
| 4. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL2533-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). |
| 5. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL2533-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY. |
| 6. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL7849-R16 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). |
| 7. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY |
| CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER TO UPDATE PRODUCT |
| APPROVAL TO THE CURRENT APPROVED VERSION |
| FL2533-R36; INCLUDE UPDATED SYSTEM NUMBER TO BE USED. |
| 8. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE METAL TO BE USED. (FL5374-R6) |
| 9. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| SUBMITTING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |