2022-12-14 13:45:20 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| NFPA 70 2017 EDITION |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW |
| |
| 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. |
| NEC 215.2, 220, 408.30 |
| |
| 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON |
| MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN |
| ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315 |
| |
| 3. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER |
| NEC 440.14 OR IRC E4101.5 |
| DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN |
| SIGHT FROM AND READILY ACCESSIBLE??? FROM THE |
| AIR-CONDITIONING EQUIPMENT. |
| |
| 4. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 |
| THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION |
| FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS |
| APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING |
| OCCUPANCIES |
| |
| 5. A ONE-LINE DIAGRAM SHOWINGS SERVICE EQUIPMENT, |
| SERVICE-ENTRANCE CONDUCTORS, SERVICE DISCONNECT, |
| SERVICE OVERCURRENT PROTECTION, MAIN POWER FEEDER, |
| FEEDER CONDUCTORS, PANELBOARDS A AND B, MAIN BONDING |
| JUMPER, AND GROUNDING ELECTRODE |
| CONDUCTOR PER NEC 230 AND 250 |
| |
| END OF COMMENTS |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |