Plan Review Notes
Plan Review Notes For Permit 22111044
Permit Number 22111044
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-11 11:25:281ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: VALUE WAS ADJUSTED TO $108,284 PER THE ICC
 BUILDING VALUATION DATA.
  
 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 3.PROVIDE THE ENERGY CALCULATIONS PER FBC EC
 R101.5.1.1.
  
 4.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7.
 R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES
 (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET (2.8 M2).
  
 5.ROOF VENTILATION
 R806.1VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 6.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPEC. SHEET OF A FLUID APPLIED MEMBRANE.
 R703.4
 APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED
 MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING
 SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTRUCTIONS.
  
 7. PROVIDE VENTILATION FOR THE BATHROOM PER
 R303.3BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 8.PROVIDE SMOKE ALARMS.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  