Plan Review Notes
Plan Review Notes For Permit 22110968
Permit Number 22110968
Review Stop P
Sequence Number 1
Notes
Date Text
2022-12-16 17:23:561ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110968
 12/16/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-001: SHOW THE INSTA-HOT WATER HEATER AND
 PIPING CONNECTIONS IN THE APPLIANCE DOMESTIC WATER
 SUPPLY DETAIL.
  
 A) SHOW THE COLD WATER LINE CONNECTION AND FULL OPEN
 SHUT OFF VALVE- SEC. 503.1 FBC P.
  
 B) SHOW A MEANS OF LIMITING THE HOT WATER TEMPERATURE,
 TYPICALLY A ASSE APPROVED MIXING VALVE- SEC. 607. AND A
 MEANS OF LIMITING THE HOT WATER TEMPERATURE- SEC.
 607.1.1. FBC P.
  
 2) P-001 & P-501: THE SINK DETAIL AND RISER ON P-001 DO
 NOT SHOW THE SINK WASTE PUMP SPECIFIED ON P-501. REFER
 TO SECS. 712.1, 712.2, & 712.3.5 FBC P AND RECISE THE
 DRAWINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  