2022-12-20 15:11:13 | 1ST REVIEW FMC | | PERMIT: 22110968 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | OCCUPANCY CLASSIFICATION BASED ON THE OCCUPANCY DENSITY | | OF TABLE 403.3.1.1. FMC 403.3.1.1 | | | | 2) LABEL THE CAV/VAV???S IN THE TERMINAL BOX SCHEDULE | | ON SHEET M-401 AND IDENTIFY EACH ON SHEET M-501. FBC | | 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|