2022-12-27 14:17:38ELECTRIC REVIEW FAILED
 1) IT APPEARS THE NUMBER OF RECEPTACLES , IN A MEETING
 ROOM, FOR FIXED WALLS, INDICATED ON ELECTRIC FLOOR PLAN
 IS NOT IN COMPLIANCE WITH NEC 210.71 . PLEASE CORRECT
 AS APPLICABLE.
 2) PLEASE INDICATE THE REQUIRED GFI PROTECTION FOR
 RECEPTACLES WITHIN 6 FEET FROM SINK, IN LOUNGE ON
 ELECTRIC FLOOR PLAN AS REQUIRED BY 210.8(B)(5)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  