Plan Review Notes For Permit 22110889 |
Permit Number |
22110889 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-29 16:06:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 301 PROVIDE A STRUCTURAL DETAIL FOR THE | | GENERATOR PAD, INCLUDING WIND DESIGN CRITERIA AND | | ANCHORING TO RESIST SPECIFIED WIND LOADS. | | | | 2. FBC R 303.5.1, OUTDOOR AIR INTAKE OPENINGS SHALL BE | | LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY | | HAZARDOUS OR NOXIOUS CONTAMINANT. REVISE PLAN TO SHOW | | DISTANCE FROM GENERATOR EXHAUST TO CLOSEST OPENING. |
|