2022-12-29 16:06:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301 PROVIDE A STRUCTURAL DETAIL FOR THE
 GENERATOR PAD, INCLUDING WIND DESIGN CRITERIA AND
 ANCHORING TO RESIST SPECIFIED WIND LOADS.
  
 2. FBC R 303.5.1, OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT. REVISE PLAN TO SHOW
 DISTANCE FROM GENERATOR EXHAUST TO CLOSEST OPENING.