2023-03-06 15:38:24 | NEW 2 STORY OFFICE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOFING | | SYSTEM - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES ON THE | | PRODUCT APPROVAL. | | | | 2) FRONT PAGE OF THE PRODUCT APPROVAL (FL16554) FOR THE | | WINDOW - "APPLICATION STATUS" SHOWS "PENDING FBC | | APPROVAL" - THE FRONT PAGE OF THE PRODUCT APPROVAL | | "APPLICATION STATUS" SHOULD SHOW "APPROVED". | | | | 3) DRAWINGS G-001, G-002, LS-101, LS - 102, ALL OF THE | | ARCHITECTURAL DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED | | IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | E-SIGNATURE). | | | | | | | | | | | | |
|