Plan Review Notes
Plan Review Notes For Permit 22110873
Permit Number 22110873
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-04 12:41:371ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE P-101 -- 2020 FPC 914.1 - THE ISOMETRIC SHOWS
 THE UPSTAIRS GROUP'S STACK DISCHARGING TO THE HIGH SIDE
 OF THE CIRCUIT VENT THAT SERVES THE DOWNSTAIRS GROUP. A
 STACK CANNOT CONNECT TO THE CIRCUIT VENT. FIXTURES ARE
 ALLOW TO BE CIRCUIT VENTED WHEN CONNECTED TO A
 HORIZONTAL BRANCH DRAIN. THE CONNECTION OF A STACK AT
 THAT LOCATION TURNS THAT PORTION OF THE DRAIN INTO A
 BUILDING DRAIN. THE UPSTAIRS STACK WOULD NEED TO
 CONNECT DOWNSTREAM OF THE CIRCUIT VENT SYSTEM.
  
 2. PAGE P-101 -- FD-2 - THE FLOOR DRAIN ON THE END OF
 THE RUN IS NOT VENTED. WHEN CONNECTED TO A BUIILDING
 DRAIN, IT NEEDS TO BE VENTED.
  
 3. 2017 WPB AMENDS 107.3.5.1.3 - THE ROOF DRAINAGE
 APPEARS TO TERMINATE ONTO THE CANOPIES. I AM UNABLE TO
 LOCATE THE GUTTER/DOWNSPOUT SIZES FOR THE CANOPIES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved