Plan Review Notes
Plan Review Notes For Permit 22110873
Permit Number 22110873
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-12-12 14:51:48THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) THE TABLE ON THE LIFE SAFETY PLAN INDICATES THIS
 BUILDING BEING CLASSIFIED AS MIXED, SEPARATED OCCUPANCY
 BUT YOU HAVE LISTED 0-HOUR SEPARATION ON THE TABLE.
 PLEASE CLARIFY THIS WITH THE REFERENCE TO THE FOLLOWING
 ACCORDING TO NFPA 101 CHAPTER 6,
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES
 ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE BARRIERS.
  
 2) CLARIFY THE ALREADY LISTED SEPARATION WITH THE
 REQUIREMENTS OF TABLE 6.1.14.4.1.
  
 3) THERE ARE WINDOWS SHOW ON FIRE RATED WALLS WITH NO
 RATING. PLEASE INDICATE THE RATING OF THE WINDOWS.
  
 4) A LIFE SAFETY PLAN MUST CLEARLY ILLUSTRATE THE
 COMMON PATH OF TRAVEL AND TRAVEL DISTANCES, PER NFPA
 101 CHAPTER 7.
  
 5) A GATE IS INDICATED ON THE PLANS PLEASE INDICATE THE
 PROVIDED FIRE DEPARTMENT ACCESS.
  
 6) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP
 DRAWING COMPLIANT WITH NFPA 72 IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]
  