2022-12-12 14:51:48 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, |
| FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THE TABLE ON THE LIFE SAFETY PLAN INDICATES THIS |
| BUILDING BEING CLASSIFIED AS MIXED, SEPARATED OCCUPANCY |
| BUT YOU HAVE LISTED 0-HOUR SEPARATION ON THE TABLE. |
| PLEASE CLARIFY THIS WITH THE REFERENCE TO THE FOLLOWING |
| ACCORDING TO NFPA 101 CHAPTER 6, |
| 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| THE OCCUPANCIES |
| ARE INTERMINGLED. |
| 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE BARRIERS. |
| |
| 2) CLARIFY THE ALREADY LISTED SEPARATION WITH THE |
| REQUIREMENTS OF TABLE 6.1.14.4.1. |
| |
| 3) THERE ARE WINDOWS SHOW ON FIRE RATED WALLS WITH NO |
| RATING. PLEASE INDICATE THE RATING OF THE WINDOWS. |
| |
| 4) A LIFE SAFETY PLAN MUST CLEARLY ILLUSTRATE THE |
| COMMON PATH OF TRAVEL AND TRAVEL DISTANCES, PER NFPA |
| 101 CHAPTER 7. |
| |
| 5) A GATE IS INDICATED ON THE PLANS PLEASE INDICATE THE |
| PROVIDED FIRE DEPARTMENT ACCESS. |
| |
| 6) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE |
| DONE BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP |
| DRAWING COMPLIANT WITH NFPA 72 IS REQUIRED TO BE |
| SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION |
| BUREAU PRIOR TO ANY INSTALLATION. |
| |
| |