2022-12-16 16:28:23FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE SUBMITTAL OF ATS, AND GENERATOR AS PER FBC
 107.2.1
  
 2. PROVIDE AVAILABLE SHORT CIRCUIT CURRENT TO FULFILL
 WITH NEC 110.9, 110.10, & 110.24
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
  