2023-01-10 16:21:22 | NEW 2 STORY OFFICE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DRAWING G-001 AND LS-101 - BUILDING DATA SHOWS RISK |
| CATEGORY III - DRAWING S-001 DESIGN CRITERIA SHOWS |
| BUILDING RISK CATEGORY II - PLEASE CLARIFY - ALL |
| DRAWINGS SHOULD MATCH. |
| |
| 2) SOME DRAWINGS SAY "NOT FOR CONSTRUCTION" CANNOT HAVE |
| THAT NOTE ON THE DRAWINGS (LS101, LS102 PLEASE CHECK |
| ALL). |
| |
| 3) PLEASE PROVIDE RAMP DETAIS - RAMP WIDTH, RAMP SLOPE, |
| LANDING SIZE AT RAMP TURN, EDGE PROTECTION ETC. FBC A |
| 405 |
| |
| 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE ROOFING SYSTEMS. |
| |
| 5) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL |
| FRONT PAGE FOR (FL16554) WINDOW PRODUCT APPROVAL. |
| |
| 6) PLEASE SHOW THE BUILDING SETBACKS FROM THE PROPERTY |
| LINES ON THE SITE PLAN. FBC WPB 107.2.5 |
| |
| 7) PLEASE SHOW THE ROOF SLOPE FBC 1507.6.2 |
| |
| 8) ACCESSIBLE RESTROOM - THE MAXIMUM DIMENSION FOR THE |
| MIRROR FROM THE FLOOR TO THE BOTTOM OF THE REFLECTIVE |
| SURFACE SHOULD BE 40 INCHES - FBC A 603.3 |
| |
| 9) BAY 1 AND BAY 2 EXPOSED INSULATION - FBC 720.3 |
| EXPOSED INSTALLATION. |
| INSULATING MATERIALS, WHERE EXPOSED AS INSTALLED IN |
| BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| |
| 10) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING |
| BUILDING DEMO., FENCES, PARKING LOT. |