2022-12-15 15:37:31 | RE-ROOF RESIDENTIAL, THIRD BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22110836 |
| 705 PALM BEACH LAKES BLVD |
| |
| ORIGINAL COMMENT: |
| 2-PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE |
| NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. |
| |
| RESPONSE: |
| REPEAT COMMENT. THREE TIMES. NOT ADDRESSED. |
| |
| |
| 3- FLAT ROOF NOA 18-0919.12 SUBMITTED: |
| A)NEED TO SPECIFY/MARK WHICH APPROVED ASSEMBLY IS GOING |
| TO BE INSTALLED. |
| |
| EMAIL RESPONSE FROM PERMIT LADI STATES "I HAVE CHECKED |
| AND THE MODIFIED BIT NOA IS INCLUDED. WE ARE USING |
| PAGES 61-63, INSTALLATION OPTION 7." |
| |
| THIS RESPONSE DOESN'T ANSWER WHICH APPROVED ASSEMBLY IS |
| GOING TO BE INSTALLED. THERE ARE SEVERAL ASSEMBLIES ON |
| PAGES 61-63 AND THERE IS NOT "INSTALLATION OPTION 7". |
| |
| NEED TO SPECIFY OR MARK WHICH ANCHOR SHEET FASTENING |
| OPTION IS GOING TO BE INSTALLED. NOTE: IF THE SPECIFIED |
| FASTENING OPTION DON'T MEET THE DESIGN PRESSURES FOR |
| ALL ROOF ZONES, THEN ENGINEER'S SIGNED AND SEALED RAS |
| 117 CALCULATIONS ARE REQUIRED (THIS IS REQUIRED BY |
| GENERAL LIMITATION #7 STATED ON EACH FASTENING OPTION). |
| |
| NOTE: ONLY FASTENING OPTION #5 ON PAGE 61 OF 67 AND |
| FASTENING OPTION #5 ON PAGE 63 OF 67 MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES IN THIS PROJECT. IF THIS |
| ASSEMBLY IS SELECTED, THEN RAS 117 CALCULATIONS ARE NOT |
| REQUIRED. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |