2022-12-15 09:35:19 | 12/15/22 REVISED COMMENTS. |
| |
| RE-ROOF RESIDENTIAL, BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22110836 |
| 705 PALM BEACH LAKES BLVD |
| |
| |
| 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY F.A.C. |
| 61G20-3.001 FOR: |
| |
| A)OK. |
| |
| ORIGINAL COMMENT: |
| B)ROOFING UNDERLAYMENT. NOTE: COORDINATE WITH ITEM #2 |
| BELOW. |
| |
| RESPONSE: |
| NOA 18-0919.12 SUBMITTED IS FOR MODIFIED BITUMEN ROOF |
| SYSTEMS (FLAT ROOF ASSEMBLIES) NOT A SHINGLES |
| UNDERLAYMENT. NEED TO SUBMIT PRODUCT APPROVAL FOR |
| UNDERLAYMENT DESIGNED FOR SHINGLES UNDERLAYMENT. NOTE: |
| COORDINATE WITH ITEM #2 BELOW. |
| |
| 12/15/22 REVISED COMMENTS. |
| PERMIT APPLICATION CALLS ONLY FOR SHINGLES RE-ROOF. IT |
| DIDN'T MENTIONED THE FLAT ROOF. AFTER LOOKING AT THE |
| ROOF REPORT SUBMITTED ON 12/9/22 IT WAS FOUND THAT REAR |
| STRUCTURE HAS A FLAT ROOF. |
| FLAT ROOF NOA 18-0919.12: NEED TO SPECIFY WHICH |
| APPROVED ASSEMBLY FROM PAGE 63 OF 67 IS GOING TO BE |
| INSTALLED AND NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7. SEE |
| LAST PAGE OF NOA FOR GENERAL LIMITATION #7 |
| REQUIREMENTS. |
| |
| |
| ORIGINAL COMMENT: |
| 2- PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH |
| THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |