2023-01-10 09:40:152ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22110830
 1/19/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #3 & #4
 FROM THE 1ST REVIEW ARE PRINTED BELOW WITH ADDITIONAL
 NOTES. PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU
 HAVE QUESTIONS.
  
 3) FAILED. P1 & P4: INDICATE HOW COMBUSTION AIR WILL BE
 PROVIDED TO THE RANGE AND FIREPLACE AND PROVIDE
 CALCULATIONS- SECTION G2407.1 FBC RES. THE CALCULATIONS
 ARE INCORREECT BASED ON THE FLOOR PLANS AND ELEVATION
 MEASUREMENTS SHOWN ON THE PLANS- REFER TO SHEETS A1.01,
 A3.01, & A3.02. USING THE STANDARD METHOD OF 50 CU. FT.
 PER 1000 BTUS, THE PLANS INDICATE A DEFICIENCY OF 956
 CU. FT. OF VOLUME FOR THE COMBINED TOTAL 182,000 BTUS
 (RANGE 132,000 + FIREPLACE- 50,000). COMBUSTION AIR
 REQUIRED- 9100 CU. FT. SHEET A1.01 INDICATES FLOOR PLAN
 LENGTH AND WIDTH OF 39.66 X 25.66= 1018 SF. X 8 FT.
 HIGH CEILINGS= 8144 CU. FT. CONCERNING THE DRYER SEE
 SHEET A1.02, A3.01, A3.03. USING THE STANDARD METHOD
 1000 CU. FT OF COMBUSTION AIR IS REQUIRED. THE ENCLOSED
 ROOM WITH DOOR PROVIDES 344 CU.FT. WHICH IS DEFICIENT,
 HOWEVER BASED ON SEC. G2407.1 EXCEPTION- TYPE 1 DRYERS
 CAN BE PROVIDED WITH MAKEUP AIR FOR EXHAUST IN
 COMPLIANCE WITH G2439.1. PLEASE CLARIFY HOW THE DRYER
 IS MEETING COMPLIANCE FOR MAKEUP AIR BASED ON SEC.
 G2439.5. IT APPEARS A JUMPER HAS BEEN INSTALLED HOWEVER
 THAT METHOD IS NOT IN COMPLIANCE WITH SEC. G2439.5
 PRINTED BELOW. PLEASE NOTE SEC. G2439.1 SPECIFIES DRYER
 EXHAUST SYSTEM INCLUDING MAKEUP AIR SHALL BE IN
 ACCORDANCE WITH MAN. SPECS.
  
 G2439.5 (614.6) MAKEUP AIR.
 INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09 M3/S)
 SHALL BE PROVIDED WITH MAKEUP AIR. WHERE A CLOSET IS
 DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN
 OPENING HAVING AN AREA OF NOT LESS THAN 100 SQUARE
 INCHES (0.0645 M2) FOR MAKEUP AIR SHALL BE PROVIDED IN
 THE CLOSET ENCLOSURE, OR MAKEUP AIR SHALL BE PROVIDED
 BY OTHER APPROVED MEANS.
  
  
 4) FAILED. P1 & P4: PROVIDE A VENTING PLAN FOR THE
 FIREPLACE INCLUDING A VENTING DIAGRAM SHOWING THE TYPE
 AND SIZE OF VENT FLUE, VENT RUN LENGTH AND TERMINATION
 LOCATION- SECS. G2427.1 & G2434.1 & G2435.1 FBC RES.
  
 THE ENGINEER'S NARRATIVE REFERS TO SHEET M1 WHICH SHOWS
 THE FIRE PLACE VENT FLUE AS EXISTNG. I HAVE RESEACHED
 THE WPB BUILDING DEPT. PERMITTING RECORDS AND I WAS
 UNABLE TO FIND A PERMIT FOR A GAS FIREPLACE OR VENT
 FLUE. PLEASE PROVIDE THE REQUESTED INFORMATION BELOW.
 PLEASE NOTE THE VENTING SYSTEM SHALL BE IN COMPLIANCE
 WITH THE MANUFACTURER'S GUIDELINES PER SEC. G2427.1 FBC
 RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  