2023-01-10 09:40:15 | 2ND REVIEW FBC-2020 FUEL GAS |
| PERMIT- 22110830 |
| 1/19/23 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #3 & #4 |
| FROM THE 1ST REVIEW ARE PRINTED BELOW WITH ADDITIONAL |
| NOTES. PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU |
| HAVE QUESTIONS. |
| |
| 3) FAILED. P1 & P4: INDICATE HOW COMBUSTION AIR WILL BE |
| PROVIDED TO THE RANGE AND FIREPLACE AND PROVIDE |
| CALCULATIONS- SECTION G2407.1 FBC RES. THE CALCULATIONS |
| ARE INCORREECT BASED ON THE FLOOR PLANS AND ELEVATION |
| MEASUREMENTS SHOWN ON THE PLANS- REFER TO SHEETS A1.01, |
| A3.01, & A3.02. USING THE STANDARD METHOD OF 50 CU. FT. |
| PER 1000 BTUS, THE PLANS INDICATE A DEFICIENCY OF 956 |
| CU. FT. OF VOLUME FOR THE COMBINED TOTAL 182,000 BTUS |
| (RANGE 132,000 + FIREPLACE- 50,000). COMBUSTION AIR |
| REQUIRED- 9100 CU. FT. SHEET A1.01 INDICATES FLOOR PLAN |
| LENGTH AND WIDTH OF 39.66 X 25.66= 1018 SF. X 8 FT. |
| HIGH CEILINGS= 8144 CU. FT. CONCERNING THE DRYER SEE |
| SHEET A1.02, A3.01, A3.03. USING THE STANDARD METHOD |
| 1000 CU. FT OF COMBUSTION AIR IS REQUIRED. THE ENCLOSED |
| ROOM WITH DOOR PROVIDES 344 CU.FT. WHICH IS DEFICIENT, |
| HOWEVER BASED ON SEC. G2407.1 EXCEPTION- TYPE 1 DRYERS |
| CAN BE PROVIDED WITH MAKEUP AIR FOR EXHAUST IN |
| COMPLIANCE WITH G2439.1. PLEASE CLARIFY HOW THE DRYER |
| IS MEETING COMPLIANCE FOR MAKEUP AIR BASED ON SEC. |
| G2439.5. IT APPEARS A JUMPER HAS BEEN INSTALLED HOWEVER |
| THAT METHOD IS NOT IN COMPLIANCE WITH SEC. G2439.5 |
| PRINTED BELOW. PLEASE NOTE SEC. G2439.1 SPECIFIES DRYER |
| EXHAUST SYSTEM INCLUDING MAKEUP AIR SHALL BE IN |
| ACCORDANCE WITH MAN. SPECS. |
| |
| G2439.5 (614.6) MAKEUP AIR. |
| INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09 M3/S) |
| SHALL BE PROVIDED WITH MAKEUP AIR. WHERE A CLOSET IS |
| DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN |
| OPENING HAVING AN AREA OF NOT LESS THAN 100 SQUARE |
| INCHES (0.0645 M2) FOR MAKEUP AIR SHALL BE PROVIDED IN |
| THE CLOSET ENCLOSURE, OR MAKEUP AIR SHALL BE PROVIDED |
| BY OTHER APPROVED MEANS. |
| |
| |
| 4) FAILED. P1 & P4: PROVIDE A VENTING PLAN FOR THE |
| FIREPLACE INCLUDING A VENTING DIAGRAM SHOWING THE TYPE |
| AND SIZE OF VENT FLUE, VENT RUN LENGTH AND TERMINATION |
| LOCATION- SECS. G2427.1 & G2434.1 & G2435.1 FBC RES. |
| |
| THE ENGINEER'S NARRATIVE REFERS TO SHEET M1 WHICH SHOWS |
| THE FIRE PLACE VENT FLUE AS EXISTNG. I HAVE RESEACHED |
| THE WPB BUILDING DEPT. PERMITTING RECORDS AND I WAS |
| UNABLE TO FIND A PERMIT FOR A GAS FIREPLACE OR VENT |
| FLUE. PLEASE PROVIDE THE REQUESTED INFORMATION BELOW. |
| PLEASE NOTE THE VENTING SYSTEM SHALL BE IN COMPLIANCE |
| WITH THE MANUFACTURER'S GUIDELINES PER SEC. G2427.1 FBC |
| RES. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |