2022-11-22 12:50:31 | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 22110830 | | 11/22/22 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS P1 & P4: A SEPARATE PERMIT IS REQUIRED FOR | | INSTALLATION OF THE GENERATOR. PLEASE LABEL THE | | GENERATOR AS "FUTURE GENERATOR"ON THE PLANS AND PROVIDE | | A GAS-TIGHT CAP FOR THE SUPPLY PIPE- SEC. 107.2.1 WPB, | | AND SEC. G2415.15 FBC RES. | | | | 3) P1 & P4: INDICATE HOW COMBUSTION AIR WILL BE | | PROVIDED TO THE RANGE AND FIREPLACE AND PROVIDE | | CALCULATIONS- SECTION G2407.1 FBC RES. | | | | 4) P1 & P4: PROVIDE A VENTING PLAN FOR THE FIREPLACE | | INCLUDING A VENTING DIAGRAM SHOWING THE TYPE AND SIZE | | OF VENT FLUE, VENT RUN LENGTH AND TERMINATION LOCATION- | | SECS. G2427.1 & G2434.1 & G2435.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|