2022-11-22 16:37:56PROVIDE A COMPLETE SCOPE OF WORK FOR THE MECHANICAL
 REVISIONS ON THIS PROJECT. THE ORIGINAL DRAWINGS DIDN'T
 SHOW MANY DUCTS AND REFERENCED THE AHU'S WERE EXISTING.
 THE KEYNOTES STATING THIS HAVE BEEN REMOVED. DOES THIS
 MEAN THERE ARE 2 NEW UNTS BEING INSTALLED? THERE ARE
 SEVERAL DUCTS SHOWN ON THIS NEW PLAN. DOES THIS MEAN
 THERE HAVE BEEN DUCTS ADDED TO THE SCOPE OF WORK? THE
 VALUE OF THIS REVISION HAS NA, IS THIS STATING THAT
 THIS EXTRA WORK DOES NOT COST ANYTHING? PLEASE PROVED A
 SCOPE OF WORK, DRAWINGS THAT HAVE THE CHANGES CLOUDED
 AND AN ACCURATE DESCRIPTION OF THE CHANGES FOR THIS
 REVISION. PLEASE ALSO CORRECT THE VALUE OF THIS
 REVISION. FBC 107.3.5
  