2023-02-09 12:44:49 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF |
| DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW |
| SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD |
| OF PROVIDING POSITIVE DRAINAGE. THIRD REQUEST. |
| 2. FBC B 107.2.1. PLEASE CLARIFY. CONTRACT REFERENCE |
| USING INSULATION TO ACHIEVE PROPER DRAINAGE. SUBMITTED |
| FLORIDA DBPR PRODUCT APPROVAL FL1654-R30 SYSTEM NO. |
| W-213 DO NOT INCLUDE INSULATION. IF USING INSULATION, |
| PLEASE SELECT SYSTEM NO. THAT INCLUDES INSULATION. |
| SYSTEM NO. MUST MEET OR EXCEED REQUIREMENTS FOR |
| EXPOSURE CATEGORY C OF -108.17 OR PROVIDE SIGNED AND |
| SEALED ENGINEERED NAILING CALCULATION. ALL APPLICABLE |
| DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| THE PRODUCT APPROVAL DRAWINGS. SECOND REQUEST. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |