2022-12-13 09:56:27 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT THE ACTUAL TEST REPORTS FOR SOUND AND FLAME |
| SPREAD FOR THE SOUND UNDERLAYMENT FOR A 6" THICK SLAB |
| WITHOUT A CEILING BELOW IT. |
| |
| 2) SUBMIT THE FIRE TEST REPORT FOR THE LAMINATE FLOOR |
| COVERING. |
| |
| PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| SUBMITTALS: |
| |
| 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. |
| DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS |
| 107.2.1. |
| 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. |
| 3. TYPE OF PROPOSED (HARD) FINISH FLOOR COVERING (TILE, |
| LAMINATE, WOOD, MARBLE, ETC.). |
| 4. STATED VALUE OF WORK. |
| 5. DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS |
| OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED |
| CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL). |
| 6. PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT. |
| 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON |
| THE EXISTING SITE CONDITIONS. |
| 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: |
| E-84, E-90 & E-492. |
| 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| (UNLESS SUBMITTING ELECTRONICALLY) |
| |
| SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND |
| INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED |
| FOR THE APPLICABLE CONSTRUCTION CONDITIONS. |
| |
| FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| |
| SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND |
| INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED |
| FOR THE APPLICABLE CONSTRUCTION CONDITIONS. |
| |
| |
| FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II |
| CONSTRUCTION |
| 603.1 ALLOWABLE MATERIALS. |
| COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| THROUGH 603.1.3: |
| 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM |
| PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN |
| 25. |
| EXCEPTIONS: |
| 1. INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| |
| |