2022-11-18 07:25:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110694
 11/18/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION DOES INDICATE WHETHER THE
 BACKFLOW REPLACEMENT IS FOR THE POTABLE WATER SERVICE
 LINE OR FOR THE FIRE SERVICE LINE, ALTHOUGH IT APPEARS
 TO BE FOR THE FIRE LINE BECAUSE IT IS A DCDA. PLEASE
 CLARIFY AND NOTE AN RPZ BACKFLOW ASSEMBLY IS REQUIRED
 FOR POTABLE WATER SERVICES- SEC. E- WPB UTILITIES CROSS
 CONNECTION MANUAL.
  
 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF
 THE BACKFLOW- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  