2023-01-24 11:14:49 | 1ST GAS REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. PAGE FG-000 -- 2017 WPB AMENDS 107.2.1 - THE |
| REFERENCED TABLE 402.4.1(1) IS FOR .3" W.C. AND YOU'VE |
| DETAILS IT IS FOR 14" W.C. PLEASE REFERENCE A MORE |
| ACCURATE SIZE TABLE. |
| |
| 2. PAGE FG-000 -- 2020 FGC 304.6 - COMBUSTION AIR |
| CALCULATIONS SHOWN ON THE PLANS STATE THE COMBUSTION |
| AIR IN CFM'S. THE CODE ASKS FOR COMBUSTION AIR TO BE |
| PROVIDED BY SQUARE INCHES OF OPENINGS PROVIDED. PLEASE |
| RECONFIGURE THE COMBUSTION AIR TO STATE IT IN CODE |
| COMPLIANT MEASUREMENTS. |
| |
| 3. PAGE FG-300 -- 2017 WPB AMENDS 107.3.5.1.5 -- THE |
| "LOOP" DOES NOT HAVE A PIPE SIZE FOR THE LINE THAT |
| SUPPLIES THE FIXTURES (THE TOP OF THE LOOP). COULD YOU |
| PLEASE ADD THAT PIPE SIZE. THE BOTTOM SIDE OF THE LOOP |
| IS 1/2". WHAT IS THE TOP? |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |