2022-12-13 10:48:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE ARE EXIT SIGNS ON THE LIFE SAFETY SHEET; A |
| 061.00, HOWEVER, THERE ARE NO EXIT SIGNS ON ANY |
| ELECTIRCAL SHEET. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| |
| PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES |
| |
| 12.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE |
| WITH CHAPTER 7 AND |
| THIS CHAPTER. |
| |
| 12.2.10 MARKING OF MEANS OF EGRESS. |
| 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS |
| IN ACCORDANCE |
| WITH SECTION 7.10. |
| |
| PLEASE REVIEW AND PROVIDE THE APPLICABLE EXIT SIGNAGE |
| ON THE ELECTICAL PLAN SHEETS. |
| |
| |
| 1A) THERE IS AN INDICATION OF A DOUBLE SWING DOOR; |
| D112, WITH AN EXIT SIGN OVER THE MIDDLE OF IT. |
| |
| PER NFPA 101, CH 7 MEANS OF EGRESS |
| |
| 7.10.1.5 EXIT ACCESS. |
| 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| READILY VISIBLE |
| SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| EXIT IS NOT READILY |
| APPARENT TO THE OCCUPANTS. |
| |
| PLEASE ENSURE THAT THE EXIT SIGN IS MOVED TO ONE SIDE |
| IN THE DIRECTION OF TRAVEL, NOT INSTALLED OVER THE |
| MIDDLE, PER THE REQUIREMENT. |
| |
| |
| 2) SHEET D 103.00 THRU D 107.00 - THERE ARE INDICATIONS |
| OF DEMOLITION. |
| |
| THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| |
| ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| DRAWINGS. |
| |
| 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| APPLICABLE NOTE OF ACKNOWLEDGMENT ON THE DEMO SHEETS. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| THE KITCHEN HOOD & SUPPRESSION SYSTEMS SHALL BE |
| INSTALLED UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| |
| |
| THE EXIT SIGN OVER THE DOUBLE SWING DOOR; D112, IS |
| REQUIRED TO BE OVER ONE SIDE OF THE DOOR, NOT IN THE |
| MIDDLE. |