Plan Review Notes
Plan Review Notes For Permit 22110645
Permit Number 22110645
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-11-21 14:11:37THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1) PLEASE PROVIDE THE CRF (CRITICAL RADIENT FLUX) FOR
 THE SOUNDPROOFING.
  
 2) PLEASE PROVIDE THE TYPE OF FLOORING BEING PLACED ON
 TOP OF THE SOUND PROOFING AND ITS PRODUCT SPECS.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]