Plan Review Notes For Permit 22110645 |
Permit Number |
22110645 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-11-21 14:11:37 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, | | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: | | | | 1) PLEASE PROVIDE THE CRF (CRITICAL RADIENT FLUX) FOR | | THE SOUNDPROOFING. | | | | 2) PLEASE PROVIDE THE TYPE OF FLOORING BEING PLACED ON | | TOP OF THE SOUND PROOFING AND ITS PRODUCT SPECS. | | | | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN | | THE CLASSES SPECIFIED | | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE | | CRITICAL RADIANT FLUX | | REQUIREMENTS. | | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I | | INTERIOR FLOOR FINISH | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | 0.45 W/CM2, AS DETERMINED | | BY THE TEST DESCRIBED IN 10.2.7.3. | | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II | | INTERIOR FLOOR FINISH | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | 0.22 W/CM2, BUT LESS | | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN | | 10.2.7.3. | | | | | | CAITLIN L FRANCIS | | FIRE INVESTIGATOR | | WEST PALM BEACH FIRE RESCUE | | 561-804-4728 | | [email protected] |
|