2023-04-20 12:33:39 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R37 |
| (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| CONSIDER USING FL5259-R38 (NON-HVHZ). |
| 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R38 |
| (NON-HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER |
| OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT |
| LIMITATIONS. SELECT PRODUCT TYPES, ALLOWABLE |
| UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS & ATTACHMENT |
| LIMITATIONS TO BE USED; SELECT FROM TABLE 4A |
| DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS |
| OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF |
| APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. |
| 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL6332-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: COVER SHEET |
| (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| INFORMATION ABOUT THE PRODUCT). SECOND REQUEST. |
| 4. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| PLEASE NOTE: CONCRETE/CLAY TILES; ASPHALT SHINGLES CAN |
| NOT BE IN INSTALLED ON ROOFS WITH A ROOF SLOPE LESS |
| THAN 2:12. SUBMIITED ROOF DRAWING LIST ROOF SLOPE AS |
| 1:12. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |