Plan Review Notes
Plan Review Notes For Permit 22110628
Permit Number 22110628
Review Stop P
Sequence Number 3
Notes
Date Text
2023-07-19 15:02:463RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22110628
 7/19/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE A COMPLETE
 REVIEW OF THE PLUMBING SYSTEMS WAS NOT PERFORMED UNDER
 THIS FOUNDATION PERMIT, AND ADDITIONAL COMMENTS
 IMPACTING THE UNDERGROUND PIPING SYSTEMS MAY OCCUR
 UNDER THE MAIN PERMIT REVIEW.
  
 1) SHEET P200.1, P200.3, P200.5, P402A: BASED ON THE
 SCHIER SI & GI SPECIFICATIONS SHOWN ON THE DERM SHEETS
 THE GREASE INTERCEPTOR INLET AND OUTLET PIPINGS SHALL
 BE 4-INCH- SEC. 1003.3.5.1 FBC P. THE PLANS SHOW 3-INCH
 FOR FOG SYSTEMS #1 & 3.
  
 2) BUILDING A GROUND FLOOR SHEETS P200.1, .2, .3, .4,
 .5, .6: AS PREVIOUSLY REQUESTED IN THE 1ST AND 2ND
 REVIEWS PLEASE SHOW THE FOLLOWING ITEMS.
  
 A) DFU'S FOR SANITARY PIPING AT RISERS, BRANCHES AND
 MAIN BUILDING DRAINS- TABLE 710.1(1) FBC P.
  
 B) STORM DRAINAGE FLOW IN GPM FOR EACH STORM DRAIN
 BRANCH AND MAIN- TABLE 1106.2 FBC P.
  
 C) AC CONDENSATE AND WATER HEATER DISCHARGE VERTICAL
 RISER LOCATIONS AND HORIZONTAL UNDERGROUND PIPING RUNS
 AND TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1,
 504.7.2 FBC P.
  
 D) EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
  
 3) 2ND REQUEST FOR GREASE INTERCEPTOR PERMIT
 APPLICATIONS.
  
 PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT
 APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A) SHEET P402A: 2ND REQUEST TO SHOW VENTING FOR THE
 INTERCEPTORS- SEC. 1003.9 FBC P.
  
 B) P9.00- P905 DERM SHEETS: 2ND REQUEST TO PROVIDE
 HEAVY DUTY LIDS FOR THE INTERCEPTOR CLEANOUTS. PLEASE
 PROVIDE MANUFACTURER AND MODEL NUMBER OF THE LIDS- SEC.
 305.7 FBC P.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  