Plan Review Notes
Plan Review Notes For Permit 22110628
Permit Number 22110628
Review Stop P
Sequence Number 2
Notes
Date Text
2023-05-10 17:05:242ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22110628
 5/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS MANY OF THE KEY PLUMBING DRAWINGS
 INCLUDING P200.1- P.200.6 WHICH ARE THE UNDERGROUND
 DRAINAGE PIPING PLANS FOR BUILDING A HAVE NOT BEEN
 CORRECTED AND RESUBMITTED (SEE 1ST REVIEW COMMENT #4
 COPIED BELOW). RESUBMITTED IN THEIR PLACES ARE
 P.200.1A- P200.6A WHICH ARE WATER AND GAS PLANS. PLEASE
 RESUBMIT THE PLANS WITH THE REQUESTED CORRECTIONS PER
 COMMENT #4.
  
 4) P200.1- P200.6 BUILDING A GROUND LEVEL PLANS:
 A) SANITARY AND STORM DRAIN PIPE SIZES MISSING- TABLES
 710.1(1), 710.1(2), 1106.2 FBC P.
 B) DFU'S FOR SANITARY PIPING NOT SHOWN- TABLE 710.1(1).
 C) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 D) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
 E) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 F) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 G) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
  
 2) 2ND REQUEST FOR POTABLE WATER BACKFLOW PERMIT
 APPLICATIONS. SHEET SP200: THE PLAN SHOWS MULTIPLE RPZ
 BACKFLOW PREVENTERS FOR THE POTABLE WATER AND FIRE
 SERVICE LINES FOR BUILDINGS WHICH WILL REQUIRE SEPARATE
 PERMIT SUBMITTALS FOR EACH ONE. CONCERNING THE RPZ'S
 FOR THE POTABLE WATER PLEASE NOTE DUE TO A CHANGE IN
 PROCESS, THE BACKFLOW PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO APPROVAL OF THIS PLUMBING REVIEW.
 YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 A) PLEASE NOTE THAT THE SEPARATE PERMIT SUBMITTALS FOR
 THE BACKFLOW PREVENTERS SHALL INCLUDE A MANUFACTURER'S
 SPECIFICATION SHEET SHOWING THE MAKE, MODEL AND SIZE OF
 THE DEVICE, AND WHICH STATES THE DEVICE IS LEAD-FREE
 AND IS ON THE APPROVED DEVICE LIST PUBLISHED BY THE
 UNIVERSITY OF SOUTHERN CALIFORNIA (USC). ALSO REQUIRED
 IS A SITE OR CIVIL SHOWING THE LOCATION OF THE BACKFLOW
 PREVENTER- SEC. 107.2.1 WPB.
  
 3) P200.7 & P.200.8: 2ND REQUEST TO PROVIDE THE STORM
 DRAINAGE FLOW IN GPM FOR EACH STORM DRAIN BRANCH AND
 MAIN- TABLE 1106.2 FBC P.
  
 4) P402A: SHOW THE LOCATION OF THE GREASE AND SOLIDS
 INTERCEPTORS ON THE SANITARY DRAINAGE FLOOR PLANS- SEE
 COMMENT #1 ABOVE.
 PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT
 APPLICATIONS TBD (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
 GREASE INTERCEPTOR PLAN REVIEW REQUIREMENTS.
  
 A) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND
 CAPACITY OF THE UNIT.
 B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 C) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL
 VENTS, AND SAMPLING PORTS.
 D) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P.
 E) ACCESS LID DETAILS INDICATING THE LIDS WILL BE HEAVY
 DUTY TRAFFIC RATED AND WILL BE EQUIPPED WITH ACCESS
 RESTRICTORS. HEAVY DUTY LIDS ARE ALSO REQUIRED FOR
 CLEANOUTS, AND SAMPLING PORTS (IF INSTALLED).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  