Plan Review Notes
Plan Review Notes For Permit 22110628
Permit Number 22110628
Review Stop E
Sequence Number 2
Notes
Date Text
2023-05-17 16:00:41ELECTRIC REVIEW FAILED 2ND CYCLE
  
 1) SUBMITTAL DOES NOT INCLUDE ALL DRAWINGS INDICATED ON
 PLAN INDEX SHEET CS001. MISSING DRAWINGS INCLUDE ALL
 ELECTRICAL DRAWINGS E202.1 -E202.8 . THESE DRAWINGS ARE
 ALSO REFERENCED ON SHEET E200.
  
 2) PLEASE PROVIDE SHEETS LABELED E200.1 AND E200.3
 (SECTIONS OF BUILDING A). FBC 107.2
  
 3) SHEET E501B, CORRECTLY LABELED, ELECTRICAL RISER
 DIAGRAM BUILDING A, AND IS AGAIN LABELED BELOW THE
 DIAGRAM AS BUILDING B. IN ADDITION THE SUBMITTAL NAME
 IS CALLED OUT INCORRECTLY AS RISER B. PLEASE CORRECT AS
 APPLICABLE. FBC 107.2
  
 4) PLEASE CORRECT LABELING FOR SHEET E502A SUBMITTAL
 NAME INDICATES RISE INSTEAD OF CORRECTLY NAMING
 ELECTRIC CALCS AND RISER NOTES
  
 5) PLEASE ENSURE ALL SHEET NAMES ARE CORRECTLY LABELED
 ON SHEETS AND SUBMITTAL NAMING. FBC 107.2
  
 6) PLEASE PROVIDE ELECTRIC RISER DIAGRAM FOR BUILDING
 C. FBC 107.2
  
 7) PLEASE PROVIDE INDICATIONS THAT ALL OVERCURRENT
 PROTECTION RATED 1200 AMPS AND ABOVE CONTAIN ARC ENERGY
 REDUCTION METHOD IN ACCORDANCE WITH NEC 240.87 (A) AND
 (B)
  
 8) PLEASE PROVIDE INDICATIONS THAT ALL FEEDER
 DISCONNECTS RATED 1000 AMPS AND ABOVE, FOR SYSTEMS OF
 MORE THAN 150 VOLTS TO GROUND ARE PROVIDED WITH GROUND
 FAULT PROTECTION. NEC 215.10 NEC
  
 9) PLEASE PROVIDE FLOOR PLANS FOR BOTH ELECTRIC ROOMS
 IN BUILDING A, B AND C LOCATING ALL ELECTRICAL
 EQUIPMENT AND INDICATING ALL CLEARANCES REQUIRED IN
 ACCORDANCE WITH NEC 110.26 ARE MET. FBC 107.2
  
 10) PLEASE PROVIDE FLOOR PLANS FOR FIRE PUMP ROOM IN
 BUILDING A LOCATING ALL EQUIPMENT AND INDICATING ALL
 REQUIREMENTS OF NEC ARTICLE 695 ARE MET. FBC 107.2
  
 11) PLEASE PROVIDE FLOOR PLANS FOR GENERATOR ROOM IN
 BUILDING A LOCATING ALL EQUIPMENT AND INDICATING ALL
 REQUIREMENTS OF NEC ARTICLE 700, 445 AND CLEARANCES IN
 ACCORDANCE TO NEC 110.26. FBC 107.2
  
 12) PLEASE PROVIDE A NOTE STATING ALL LOW VOLTAGE
 WIRING SYSTEMS INCLUDING BUT NOT LIMITED TO FIRE ALARM,
 VOICE, DATA TELEPHONE, TV, SATELLITE, SECURITY AND BDA,
 DAS, CELL PHONE ENHANCEMENT SYSTEMS REQUIRE A SEPARATE
 PERMIT. IN ADDITION, SITE LIGHTING AND SIGNS WILL BE
 REQUIRED TO BE SEPARATE PERMITS
  
 13) PLEASE PROVIDE A FEEDER SCHEDULE FOR ALL RISER
 DIAGRAMS. NEC 215.5
  
 14) SUBMITTAL CONTAINS SOME ELECTRIC SHEETS THAT HAVE A
 RED X ON THEM. IF THESE SHEETS ARE NOT INCLUDED WITH
 THE SUBMITTAL PLEASE HAVE THEM REMOVED. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  