Plan Review Notes
Plan Review Notes For Permit 22110628
Permit Number 22110628
Review Stop P
Sequence Number 1
Notes
Date Text
2023-02-21 17:19:371ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110628
 2/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP200: THE PLAN SHOWS MULTIPLE RPZ BACKFLOW
 PREVENTERS FOR THE POTABLE WATER AND FIRE SERVICE LINES
 FOR BUILDINGS WHICH WILL REQUIRE SEPARATE PERMIT
 SUBMITTALS FOR EACH ONE. CONCERNING THE RPZ'S FOR THE
 POTABLE WATER PLEASE NOTE DUE TO A CHANGE IN PROCESS,
 THE BACKFLOW PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A) PLEASE NOTE THAT THE SEPARATE PERMIT SUBMITTALS FOR
 THE BACKFLOW PREVENTERS SHALL INCLUDE A MANUFACTURER'S
 SPECIFICATION SHEET SHOWING THE MAKE, MODEL AND SIZE OF
 THE DEVICE, AND WHICH STATES THE DEVICE IS LEAD-FREE
 AND IS ON THE APPROVED DEVICE LIST PUBLISHED BY THE
 UNIVERSITY OF SOUTHERN CALIFORNIA (USC). ALSO REQUIRED
 IS A SITE OR CIVIL SHOWING THE LOCATION OF THE BACKFLOW
 PREVENTER- SEC. 107.2.1 WPB.
  
 2) PROVIDE SANITARY DRAINAGE AND WATER RISER DRAWINGS
 FOR BUILDING A- SEC. 107.3.5.1.3 WPB.
  
 3) PROVIDE PRIMARY AND SECONDARY ROOF DRAINAGE RISER
 DRAWINGS- SEC. 107.3.5.1.3 WPB.
  
 4) P200.1- P200.6 BUILDING A GROUND LEVEL PLANS:
 A) SANITARY AND STORM DRAIN PIPE SIZES MISSING- TABLES
 710.1(1), 710.1(2), 1106.2 FBC P.
 B) DFU'S FOR SANITARY PIPING NOT SHOWN- TABLE 710.1(1).
 C) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 D) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
 E) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 F) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 G) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
  
 5) P200.7:
 A) LABEL THE WASTE AND SOIL STACK LOCATIONS USING THE
 LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 WPB.
 B) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 C) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 D) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 E) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
 F) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
  
 6) P200.8:
 A) LABEL THE WASTE AND SOIL STACK LOCATIONS USING THE
 LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 WPB.
 B) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH
 STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P.
 C) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE
 VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND
 TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2
 FBC P.
 D) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE
 PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC.
 712.3.5 FBC P.
 E) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL
 PROTECTION METHOD- SEC. 1002.4 FBC P.
 F) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION
 LOCATIONS- SEC. 1108.2 FBC P.
  
 7) P300: THERE ARE TWO P300 PLAN SHEETS APPARENTLY ONE
 FOR BUILDING B AND ONE FOR BUILDING C HOWEVER THEY ARE
 NOT TITLED PROPERLY TO DISTINGUISH ONE FROM THE OTHER-
 SEC. 107.2.1 WPB.
  
 8) P300: THE WATER RISERS ARE INCORRECTLY LABELED AS
 RAIN WATER LEADER RISERS- SEC. 107.2.1 WPB.
  
 9) P301: THERE ARE TWO P301 PLAN SHEETS APPARENTLY ONE
 FOR BUILDING B AND ONE FOR BUILDING C HOWEVER THEY ARE
 NOT TITLED PROPERLY TO DISTINGUISH ONE FROM THE OTHER-
 SEC. 107.2.1 WPB.
 A) SAN. ISO: LABEL THE WASTE AND SOIL STACK LOCATIONS
 USING THE LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1
 WPB.
 B) STORM ISO: PROVIDE THE STORM DRAINAGE FLOW IN GPM
 FOR EACH STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC
 P.
  
 10) P500 DETAIL 6: PROVIDE THE MAKE AND MODEL OF THE
 CLEANOUT ASSEMBLY SHOWN IN THE DETAIL- SEC. 708.1.10.2
 FBC P.
  
 11) P502 DETAILS 5 & 11: THE POOL SHALL BE UNDER
 SEPARATE PERMIT HOWEVER CONCERNING POOL WASTE WATER
 DISPOSAL AS SHOWN IN THE DETAILS PLEASE NOTE THE
 FOLLOWING-
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  