2023-02-21 17:19:37 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22110628 |
| 2/21/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET SP200: THE PLAN SHOWS MULTIPLE RPZ BACKFLOW |
| PREVENTERS FOR THE POTABLE WATER AND FIRE SERVICE LINES |
| FOR BUILDINGS WHICH WILL REQUIRE SEPARATE PERMIT |
| SUBMITTALS FOR EACH ONE. CONCERNING THE RPZ'S FOR THE |
| POTABLE WATER PLEASE NOTE DUE TO A CHANGE IN PROCESS, |
| THE BACKFLOW PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR |
| TO APPROVAL OF THIS PLUMBING REVIEW. YOU CAN SUBMIT AN |
| APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A |
| CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| APPLICATION TO [email protected]. YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| A) PLEASE NOTE THAT THE SEPARATE PERMIT SUBMITTALS FOR |
| THE BACKFLOW PREVENTERS SHALL INCLUDE A MANUFACTURER'S |
| SPECIFICATION SHEET SHOWING THE MAKE, MODEL AND SIZE OF |
| THE DEVICE, AND WHICH STATES THE DEVICE IS LEAD-FREE |
| AND IS ON THE APPROVED DEVICE LIST PUBLISHED BY THE |
| UNIVERSITY OF SOUTHERN CALIFORNIA (USC). ALSO REQUIRED |
| IS A SITE OR CIVIL SHOWING THE LOCATION OF THE BACKFLOW |
| PREVENTER- SEC. 107.2.1 WPB. |
| |
| 2) PROVIDE SANITARY DRAINAGE AND WATER RISER DRAWINGS |
| FOR BUILDING A- SEC. 107.3.5.1.3 WPB. |
| |
| 3) PROVIDE PRIMARY AND SECONDARY ROOF DRAINAGE RISER |
| DRAWINGS- SEC. 107.3.5.1.3 WPB. |
| |
| 4) P200.1- P200.6 BUILDING A GROUND LEVEL PLANS: |
| A) SANITARY AND STORM DRAIN PIPE SIZES MISSING- TABLES |
| 710.1(1), 710.1(2), 1106.2 FBC P. |
| B) DFU'S FOR SANITARY PIPING NOT SHOWN- TABLE 710.1(1). |
| C) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH |
| STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P. |
| D) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION |
| LOCATIONS- SEC. 1108.2 FBC P. |
| E) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE |
| VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND |
| TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2 |
| FBC P. |
| F) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE |
| PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC. |
| 712.3.5 FBC P. |
| G) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL |
| PROTECTION METHOD- SEC. 1002.4 FBC P. |
| |
| 5) P200.7: |
| A) LABEL THE WASTE AND SOIL STACK LOCATIONS USING THE |
| LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 WPB. |
| B) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH |
| STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P. |
| C) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE |
| VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND |
| TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2 |
| FBC P. |
| D) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE |
| PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC. |
| 712.3.5 FBC P. |
| E) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL |
| PROTECTION METHOD- SEC. 1002.4 FBC P. |
| F) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION |
| LOCATIONS- SEC. 1108.2 FBC P. |
| |
| 6) P200.8: |
| A) LABEL THE WASTE AND SOIL STACK LOCATIONS USING THE |
| LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 WPB. |
| B) PROVIDE THE STORM DRAINAGE FLOW IN GPM FOR EACH |
| STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC P. |
| C) SHOW THE CONDENSATE AND WATER HEATER DISCHARGE |
| VERTICAL RISER LOCATIONS AND HORIZONTAL PIPING RUNS AND |
| TERMINATION LOCATIONS- SECS. 314.2.1 & 504.7.1, 504.7.2 |
| FBC P. |
| D) SHOW THE ELEVATOR SUMP PUMP LOCATIONS AND DISCHARGE |
| PIPING RUNS TO THE SANITARY DISPOSAL LOCATIONS- SEC. |
| 712.3.5 FBC P. |
| E) SHOW EMERGENCY FLOOR DRAIN LOCATIONS AND TRAP SEAL |
| PROTECTION METHOD- SEC. 1002.4 FBC P. |
| F) SHOW THE SECONDARY ROOF DRAINAGE TERMINATION |
| LOCATIONS- SEC. 1108.2 FBC P. |
| |
| 7) P300: THERE ARE TWO P300 PLAN SHEETS APPARENTLY ONE |
| FOR BUILDING B AND ONE FOR BUILDING C HOWEVER THEY ARE |
| NOT TITLED PROPERLY TO DISTINGUISH ONE FROM THE OTHER- |
| SEC. 107.2.1 WPB. |
| |
| 8) P300: THE WATER RISERS ARE INCORRECTLY LABELED AS |
| RAIN WATER LEADER RISERS- SEC. 107.2.1 WPB. |
| |
| 9) P301: THERE ARE TWO P301 PLAN SHEETS APPARENTLY ONE |
| FOR BUILDING B AND ONE FOR BUILDING C HOWEVER THEY ARE |
| NOT TITLED PROPERLY TO DISTINGUISH ONE FROM THE OTHER- |
| SEC. 107.2.1 WPB. |
| A) SAN. ISO: LABEL THE WASTE AND SOIL STACK LOCATIONS |
| USING THE LETTER SYMBOLS SHOWN ON P300- SEC. 107.2.1 |
| WPB. |
| B) STORM ISO: PROVIDE THE STORM DRAINAGE FLOW IN GPM |
| FOR EACH STORM DRAIN BRANCH AND MAIN- TABLE 1106.2 FBC |
| P. |
| |
| 10) P500 DETAIL 6: PROVIDE THE MAKE AND MODEL OF THE |
| CLEANOUT ASSEMBLY SHOWN IN THE DETAIL- SEC. 708.1.10.2 |
| FBC P. |
| |
| 11) P502 DETAILS 5 & 11: THE POOL SHALL BE UNDER |
| SEPARATE PERMIT HOWEVER CONCERNING POOL WASTE WATER |
| DISPOSAL AS SHOWN IN THE DETAILS PLEASE NOTE THE |
| FOLLOWING- |
| SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| DEPARTMENT. |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S |
| SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |