Plan Review Notes For Permit 22110628 |
Permit Number |
22110628 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-03-07 10:22:12 | ELECTRIC REVIEW FAILED | | | | 1) PLEASE DETAIL ON SHEET E400A COMPLIANCE WITH NEC | | 695.14(E), PROTECTION OF FIRE PUMP GENERATOR CONTROL | | WIRING | | 2) PLEASE DETAIL COMPLIANCE WITH NEC 230.95, GROUND | | FAULT PROTECTION FOR 480V/2000A MDP-RS AND 480/2500A | | MDP-RN | | 3) PLEASE DETAIL COMPLIANCE WITH NEC 695.39(B) FOR | | BUILDINGS B AND C, ALTERNATE SOURCE OF POWER, AS THE | | AHJ DOES NOT REGARD FPL UTILITY POWER AS A RELIABLE | | SOURCE. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | |
|