2022-12-20 12:37:24ELECTRIC REVIEW FAILED
  
 1)PLEASE DETAIL (2) SMALL APPLIANCE KITCHEN CIRCUITS AS
 REQUIRED PER NEC 210.52
 2)IT APPEARS SOME RECEPTACLE SPACING IS DOES NOT COMPLY
 WITH NEC 210.52. PLEASE CORRECT AS APPLICABLE, IF
 RECEPTACLES ARE EXISTING PLEASE DETAIL THEM AND NOTE
 THAT THEY ARE EXISTING. FBC 107.2
 3) PLAN STATES NEW LIGHTING OUTLETS, HOWEVER NONE ARE
 SHOWN. PLEASE DETAIL AS APPLICABLE. FBC 107.2
 4) PLEASE INDICATE ALL WIRING REPLACED, MODIFIED OR
 REPAIRED. FBC 107.2
 5) PLEASE PROVIDE A DETAILED BUILDING RISER DIAGRAM
 INCLUDING ALL CONDUCTOR, EQUIPMENT, CONDUIT SIZES,
 OVERCURRENT PROTECTION SIZES AND SPECIFICATIONS AND
 GROUNDING ELECTRODE SYSTEM. NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved